It is possible and acceptable that the acceleration time exceeds the safe stall time (bearing
in mind that a locked rotor condition is quite different than an acceleration condition). In
this instance, each distinct portion of the thermal limit curve must be known and
protection coordinated against that curve. The protection relay must be able to distinguish
between a locked rotor condition, an accelerating condition, and a running condition. The
489 voltage dependent overload curve feature is tailored to protect these types of
machines. Voltage is monitored constantly during starting and the acceleration thermal