CHAPTER 5: SETPOINTS
Note

5.11.7 Running Hour Setup

RUNNING
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
POS. kvarh PULSE OUT
MESSAGE
INTERVAL: 10 kvarh
NEG. kvarh PULSE OUT
MESSAGE
RELAYS (2-5): ----
NEG. kvarh PULSE OUT
MESSAGE
INTERVAL: 10 kvarh
PULSE WIDTH:
MESSAGE
200 ms
The 489 can perform pulsed output of positive kWh and both positive and negative kvarh.
Each output parameter can be assigned to any one of the alarm or auxiliary relays. Pulsed
output is disabled for a parameter if the relay setpoint is selected as OFF for that pulsed
output. The minimum time between pulses is fixed to 400 milliseconds.
This feature should be programmed so that no more than one pulse per 600 milliseconds is
required or the pulsing will lag behind the interval activation. Do not assign pulsed outputs
to the same relays as alarms and trip functions.
normally open (NO) contact
normally closed (NC) contact
PATH: SETPOINTS
S10 MONITORING
INITIAL GEN. RUNNING
[ ]
HOURS: 0 h
GEN. RUNNING HOURS
MESSAGE
ALARM: Off
ASSIGN ALARM
MESSAGE
RELAYS (2-5): ---5
GEN. RUNNING HOURS
MESSAGE
LIMIT: 1000 h
The 489 can measure the generator running hours. This value may be of interest for
periodic maintenance of the generator. The initial generator running hour allows the user
to program existing accumulated running hours on a particular generator the relay is
protecting. This feature switching 489 relays without losing previous generator running
hour values.
Range: 1 to 50000 kvarh in steps of 1
Range: Any combination of Relays 2 to
Range: 1 to 50000 kvarh in steps of 1
Range: 200 to 1000 ms in steps of 1
status
status
OPEN
CLOSED
CLOSED
OPEN
PULSE
WIDTH
FIGURE 5–28: Pulse Output
RUNNING HOUR SETUP
Range: 0 to 999999 h in steps of 1
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to
Range: 1 to 1000000 h in steps of 1
5
status
OPEN
CLOSED
808738A1.CDR