Installation guide - ERC 213

8 - Technical Data

FEATURES
Input
Rated power
Inputs
Types of sensors allowed
Sensors in "Kit Solution"
Precision
Output
Display
Operating Conditions
Storage conditions
Protection
Environmental data
Heat and fire resistant
EMC category
Certifications
© Copyright Danfoss | Published by AZ | 2016.04
DESCRIPTION
Low voltage, regulated, galvanically isolated, 115 V AC or 230 V AC, 50/60 Hz input
Less than 0.7 W
4 Inputs:
2 analogue, 1 analogue / digital and 1 digital
NTC 5000 Ohms at 25 °C (beta = 3,980 at 25/100 °C - EKS 211 for example)
NTC 10000 Ohms at 25 °C (beta = 3,435 at 25/85 °C - EKS 221 for example)
PTC 990 Ohms at 25 °C (EKS 111 for example)
Pt1000 (AKS 11, AKS 12, AKS 21 for example)
NTC 10000 Ohms at 25 °C, 1.5 m cable
Measuring range:
-40 – 105 °C (-40 – 221 °F)
Controller accuracy:
+/-1 K below -35 °C,
+/-0.5 K between -35 – 25 °C, +/-1 K above 25 °C
Compressor relay DO1:
16 A, 16 (16) A, EN 60730
10 FLA / 60 LRA at 230 V, UL60730
16 FLA / 72 LRA at 115 V, UL60730
Defrosting relay DO2:
8 A, 2 FLA / 12 LRA, UL60730
8 A, 2 (2 A), EN60730
Fan relay DO3:
3 A, 2 FLA / 12 LRA, UL60730
3 A, 2 (2 A), EN60730
LED 3-figure display, decimal point and multifunction icons, °C + °F scale
-10 – 55 °C (14 – 131 °F), 90% Rh
-40 – 70 °C (-40 – 158 °F), 90% Rh
Front: IP65 (with seal)
Rear: IP00
Pollution degree II, condensate free
Category D (UL94-V0)
Category I
UL acknowledgement (USA and Canada) (UL 60730)
ENEC (EN 60730)
CQC
EC (LVD and EMC Directives)
EAC (GHOST)
NSF
ROHS2.0
HACCP temperature monitoring in compliance with EN134785 Class I if used with sensor AKS 12
Installation guide | ERC 213
DKRCE.PI.RL0.O2.02 / 520H11062 | 5