An E2 has three COM ports that can be assigned for
MODBUS communication (COM2). COM ports can
only be used for one function; in other words, if
COM2 is set up as the I/O network, you cannot
connect MODBUS devices to COM2. Ensure your E2
is configured in E2 General Services (
Serial tab) to enable COM4 or COM6.
Connect the MODBUS network cable to the three-
terminal connector on the COM port you wish to
assign as MODBUS. Reverse polarity of +/- on
RS485 cable from E2 to the device.
TERMINATED,
BIASED
(ALL 3 JUMPERS
IN UP POSITION)
E2
XM670/
XM679
#1
Figure 22-4 - MODBUS Networking

22.3. E2 Setup of Devices

22.3.1.Set Up Network Ports

Before setting up a device, the port on the E2 that has
the MODBUS cable connected must be set up as a
MODBUS port.
1. Log in to the E2 with Level 4 access.
2. Press
followed by
Controller Info.
3. Press
+
to open the Serial tab of the General
Controller Info setup screens:
38 • XM679K I&O Manual

,
XM670/
XM670/
XM679
XM679
#2
#3

- General
Figure 22-5 - Serial Communications Manager Screen
4. This screen will have a "Connection" field for all
COM ports on the E2. Highlight the COM port
connection field that will be used for the device, and
press  - LOOK UP. From the list of network
types, select MODBUS.
5. Four fields will become visible underneath the
COM port connection field, which pertain to the
way the device communicates:
• Baud - Default setting is 19.2k. The baud rate
setting should be set to match the baud rate of the
XM670 - XM679 device (9600). (All devices
connected to the same COM port should be set to the
same baud rate.)
• Data Size - Leave this field at the default value (8).
• Parity - Leave this field at the default value (None).
• Stop Bits - Leave this field at the default value (1).
6. Press
to save changes and exit.

22.3.2.Add and Connect the Device

To enable communications between E2 and the
XM670 - XM679 units, the devices must be added
and addressed in E2.
1. Log in to the E2 with Level 4 access.

2. Press
and Controllers.
- Connected I/O Boards
026-1218 Rev 4