Method for E2, XR, XM, and XEV Devices
Overview
To simplify MODBUS communication wiring with E2, (both Standard and Enhanced versions) XR, XM, and
XEV series devices, the alternate method outlined below may be used.
Wire Type
Use Belden 8761 or equivalent cable.
Shield
DO NOT connect the shield to the device. Keep the shield continuous throughout a network segment. The shield
must be twisted together and insulated with electrical tape or heatshrink at each device within a network
segment. Securely connect the shield to an earth grounded chassis at each end of a network segment.
Termination
Each network segment must be biased and terminated at the E2 controller's end (all three jumpers in the MOD
position for E2 Enhanced, or all three jumpers in the UP position for E2 Standard) and terminated with a 150
ohm resistor at the other end of the network segment (150 ohms between the two communication wires).
Recommended
For reliable communication on some installations, it may be necessary to connect a 100 ohm resistor between
the XR, XM, or XEV device's previously identified ground terminal and earth ground.
Some E2 MODBUS COM Ports Can Support Two Network Segments
For E2 Enhanced 4.x Controller Hardware
COM2 supports two network segments: one on connector RS485-COM2A, and the second on connector RS485-
COM2B.
COM4 supports two network segments: one on connector RS485-COM4A, and the second on connector RS485-
COM4B.
COM6 only supports one network segment on connector RS485-COM6.
For E2 Standard 3.x Controller Hardware
COM2 supports two network segments: one on connector RS485-1A, and the second on connector 
RS485-1B.
For information on the maximum recommended number of XR, XM, and XEV devices for each network segment
(load and bandwidth calculations), contact Emerson Technical Support at 770-425-2724.