18.3. E2 Setup of Devices

18.3.1.Set Up Network Ports

Before setting up a device, the port on the E2 that has the
MODBUS cable connected must be set up as a MODBUS
port.
1. Log in to the E2 with Level 4 access.
2. Press
followed by
Controller Info.
3. Press
+
to open the Serial tab of the General
Controller Info setup screens:
Figure 18-4 - Serial Communications Manager Screen
4. This screen will have a "Connection" field for all
COM ports on the E2. Highlight the COM port 
connection field that will be used for the device, and
press  - LOOK UP. From the list of network
types, select MODBUS.
5. Four fields will become visible underneath the
COM port connection field, which pertain to the
way the device communicates:
• Baud - Default setting is 19.2k. The baud rate 
setting should be set to match the baud rate of the
XR75CX device (9600). (All devices connected to
the same COM port should be set to the same baud
E2 Setup of Devices

- General
rate.)
• Data Size - Leave this field at the default value (8).
• Parity - Leave this field at the default value (None).
• Stop Bits - Leave this field at the default value (1).
6. Press
to save changes and exit.

18.3.2.Add and Connect the Device

To enable communications between E2 and the XR75CX
units, the devices must be added and addressed in E2.
1. Log in to the E2 with Level 4 access.

2. Press
and Controllers.
Num Network Ctrls: NetSetup Screen
Figure 18-5 -
3. In the Num Network Ctrls: NetSetup screen, under
the ECT tab, enter the number of devices in the
Quantity field. (Max shows the maximum number
of devices allowed on the network.)
4. Press
to return to the Network Setup menu,
then select
- Network Summary.
5. Locate the units you added to the network list (press
to scroll through the list). If desired, 
and
enter a new name for each device in the Name field.
ECT MODBUS Networking to E2s • 23