7.
Placement of the openings in the wall.
Damper assembly procedures must be done so as all load transfer from the fire separating constructions to
the damper body is absolutely excluded. Back-to-back air - conditioning piping must be hung or supported
so as all load transfer from the back-to-back piping to the damper is absolutely excluded.
8.
The fire damper can be integrated into a solid or gypsum wall construction or into solid ceiling
construction. Damper blade has to be inside of construction (labelled with BUILD IN EDGE on the
damper body).
BUIL-IN EDGE
9.
All fire dampers has to be closed during installation process. The damper body should not be deformed
in the course of bricking in. Once the damper is built in, its blade should not grind on the damper body
during opening or closing.
10. To provide needed access space to the control device, all other objects must be situated at least
350 mm from the control parts of the damper. Inspection hole must be accessible.
BUILT-IN EDGE