SECTION 5 - COMMISSIONING
FORM155.31-CL1.EN.UL
ISSUE DATE: 12/21/2018
DOUBLE EFFECT STEAM ABSORPTION CHILLER COMMISSIONING DATA SHEET (1/2)
User:
Model:
Insulation Resistance
Standard: 5 MΩ or more (with 500 V
megger)
Circuit breaker
Solution circulation pump
Solution spray pump
Refrigerant pump
Purge pump
Thermal Relay Setting
Solution circulation pump
Solution spray pump
Refrigerant pump
Purge pump
Pump Discharge Pressure
Solution circulation pump
Solution spray pump
Refrigerant pump
NOTES:
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
JOHNSON CONTROLS
102
MFG.No.:
R-Gnd
S-Gnd
MΩ
U-Gnd
V-Gnd
MΩ
MΩ
MΩ
MΩ
Refrigerant Purity
A
Standard: 1.040 (kg/L) or less
A
Specific gravity
A
Turbidity
A
Purge Amount
PSIG
Standard: 4 cc/min or less
PSIG
Purge tank
PSIG
Absorber
FORM 155.31-ICOM2.EN.UL
User's machine code:
Electric Power Supply
T-Gnd
Specification: AC
Standard: Within +/- 10% of spec.
R-S
W-Gnd
R-T
S-T
R-Gnd
S-Gnd
T-Gnd
Temperature Setting
Set base temp.
Auto. stop temp.
Auto restart diff.
cc
cc
ISSUE DATE: 12/21/2018
V /
Hz
V
V
V
V
V
V
°F
°F
°F
5
JOHNSON CONTROLS