Section 4 - Technical Data; Table 6 - Typical Operational Range - York YHAU-CW Manual

Double effect steam-fired absorption chiller
Table of Contents

Advertisement

FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
This section includes technical information about the
unit, such as weight, dimensions, electrical data, wir-
ing, and sound data.

TABLE 6 - TYPICAL OPERATIONAL RANGE

PARAMETER
Chilled Water In
Chilled Water Out
Cooling Water In
Cooling Water Out
Steam Inlet Pressure
Condensate Outlet
JOHNSON CONTROLS

SECTION 4 - TECHNICAL DATA

ALLOWABLE RANGES
44.6 – 77°F
39.2 – 60.8°F
68 – 98.6°F
77 – 107.6°F
29 ~ 145 PSIG
~140°F
The numbers shown in Table 6 on page 37 are the
allowable ranges for each parameter. Not all combi-
nations are possible. Please check with your Johnson
Controls Service Center to see if your temperature dif-
ferential is possible.
4
37