Chapter 1
Table 1. Eaton 5125 Battery Runtimes (in Minutes)
Load
900W
1350W
1800W
2250W
2700W
3150W
3600W
4050W
4500W
Load
1080W
1620W
2160W
2700W
3240W
3780W
4320W
4860W
5400W
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Eaton 240V Extended Battery Module (EBM 240) User's Guide
Introduction
The 240V Extended Battery Module (EBM 240) can be added to the
5000/6000 VA Eaton
5125 or 9125 uninterruptible power system (UPS)
®
to extend the available UPS battery time (see Table 1 or Table 2). Up to
four EBMs can be installed with either UPS.
5000 VA, 4500W Models
UPS Internal
+1 EBM
Batteries
59
169
39
108
26
79
19
61
15
49
12
41
9
31
8
27
7
24
6000 VA, 5400W Models
UPS Internal
+1 EBM
Batteries
49
138
33
88
20
64
15
49
11
40
9
33
7
25
6
22
5
19
S
+2 EBMs
303
192
138
106
85
71
60
52
46
+2 EBMs
247
156
111
85
68
57
48
42
36
164201518 Rev C www.eaton.com/powerquality
+3 EBMs
+4 EBMs
452
612
284
384
204
274
156
210
125
168
104
139
88
118
76
102
67
89
+3 EBMs
+4 EBMs
367
497
230
311
164
221
125
168
100
134
83
111
70
94
61
81
53
71