KYOWA WGA-910A Series Instruction Manual page 24

For cc-link option
Hide thumbs Also See for WGA-910A Series:

Advertisement

8-3-2. Contents of the remote output RY (M
Name
Command processing
request 1
Command processing
request 2
WRITE_READ
Measureing Condition
0 to 3
ZERO command
RESET command
HOLD command
Waveform command
TEDS command
Value selection 1
Value selection 2
Error reset request flag
R)
Turn ON when writing the pre-set values of the Measureing Condition (operation
pattern) limited data.
Before turning OFF, make sure the [Command processing response 1] is ON.
Corresponding to the [/M] command.
It is the same function as "/ M command" (Setting save command) of RS
communication.
Turn ON when writing the general commands.
Before turning OFF, make sure the [Command processing response 2] is ON.
It is the same function as "/ M command" (Setting save command) of RS
communication.
Select the WRITE/READ of the general commands.
OFF: WRITE, ON: READ
Change the Measureing Condition with the combination of ON/OFF setting from the
"Measuring condition 0" to "Measuring condition 3."
Execute the DIGITAL ZERO function at the rising edge.
During ON, keep executing the DIGITAL ZERO function.
Cancel the DIGITAL ZERO function at the falling edge.
Reset the Hold mode at the rising edge.
During ON, Keep executing the Reset function.
Cancel the Hold mode reset at the falling edge.
Control the Hold mode at the rising edge and falling edge.
When the Hold mode is "Interval-specified peak hold", in the same manner as the
control input signals, the product operates as follows.
Rising edge: Starts detecting data.
During ON: Detecting interval
Falling edge: Starts Holding interval
Waveform display starts at ON edge. ( = Start key)
Waveform display continues while ON.
Acquisition of the waveform ends at the OFF edge. ( = Stop key)
TEDS auto calibration starts on ON edge.
When the "TEDS calibration in progress" message disappears, please turn it off.
Change the value to be output, into the [Indicated value_Selection] data area of the
Remote register: R
M.
(Valid when the No. of occupied stations is 1 or 2.)
OFF: Measured value (tracking value)
ON: Holding value (indicated value)
Change hold data to Peak or Bottom.
OFF: Peak
ON: Bottom
Error state flag was turned ON by any error occurred.
Turn ON the error reset request flag when the error state flag is turned OFF.
Contents