4.7
28-Day Timer
Each 28-day timer has a Program 1 and a Program 2 for programming the various feed times.
The programming for Program 1 and 2 are the same but allow for more variation in the timer's
relay activation.
>SYSTEM 1 TIMER 1 CHANGE<
WEEKS
DAYS
START TIME
RUN TIME
PREBLEED
5.
Customize
>CUSTOMIZE<
UNIT NAME
SYS 1 NAME
SYS 2 NAME
RELAY NAMES
6.
Alarms
>ALARMS<
SYS 1 ALARMS
SYS 2 ALARMS
7.
Date and Time Set Up
>SET DATE AND TIMES<
SET DATE
SET TIME
SET DAY
SET WEEK
Friday May 18, 2002 03:04:56
WEEKS- The week(s) that the timer is to feed.
DAYS- The day(s) that the timer is to feed.
MIN COND
START-The time of day for the timer to start.
FEED LOCK
RUN- How long the timer is to run.
BLEED LOCK
PREBLEED-How long the controller is to
FLOW LOCK
bleed down before feeding in chemical.
NOTE: The prebleed starts at the START
time programmed above.
MIN COND-The minimum conductivity that
the unit will prebleed down to.
FEED LOCK-Which other system timer to
lockout during this timers run time.
BLEED LOCK-How long to lock out the
bleed function after the timer's run time.
FLOW LOCK-If the system has a flow
switch you can ignore it for this timer.
CUSTOMIZE – Allows for the user to define the
on-screen name for the Unit, System 1 and
System 2 (if applicable) as well as the names for
each relay.
ALARMS – Shows any current alarms.
DATE AND TIME - For setting the date,
time, day and week on the controller.