18.1.2

Field setting components

Location of the 7‑segment displays, buttons and DIP switches:
a
b
c
DS1 DS2
BS1 BS2
BS3
X27A
BS1
MODE: for changing the set mode
BS2
SET: for field setting
BS3
RETURN: for field setting
DS1, DS2
DIP switches
a
7-segment displays
b
Push buttons
c
DIP switches
18.1.3

To access mode 1 or 2

Initialisation: default situation
NOTICE
Turn ON the power 6 hours before operation in order to
have power running to the crankcase heater and to protect
the compressor.
Turn on the power supply of the outdoor unit and all indoor units.
When the communication between indoor units and outdoor unit(s) is
established and normal, the 7‑segment display indication state will
be as below (default situation when shipped from factory).
Stage
When turning on the power supply: blinking as
indicated. First checks on power supply are
executed (8~10 min).
When no trouble occurs: lighted as indicated
(1~2 min).
Ready for operation: blank display indication as
indicated.
Off
Blinking
On
In case of malfunction, the malfunction code is displayed on the
indoor unit user interface and the outdoor unit 7‑segment display.
Solve the malfunction code accordingly. The communication wiring
should be checked at first.
Access
BS1 is used to switch between the default situation, mode  1 and
mode 2.
Access
Default situation
Mode 1
▪ Push BS1 one time.
7‑segment display indication changes to:
▪ Push BS1 one more time to return to the
default situation.
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752781-1B – 2024.02
2" [ 4  41]
Display
Action
.
Access
Mode 2
▪ Push BS1 for at least five seconds.
7‑segment display indication changes to:
▪ Push BS1 one more time (short) to return to
the default situation.
INFORMATION
If you get confused in the middle of the process, push BS1
to return to the default situation (no indication on
7‑segment displays: blank, see
2" [ 4  41].
or
18.1.4

To use mode 1

Mode 1 is used to set basic settings and to monitor the status of the
unit.
What
Changing and accessing
1
the setting in mode 1
2
3
To quit and return to the
Push BS1.
initial status
18.1.5

To use mode 2

Mode 2 is used to set field settings of the outdoor unit and system.
What
Changing and accessing
▪ Push BS1 for more than five seconds
the setting in mode 2
to select mode 2.
▪ Push BS2 to select the required
setting.
▪ Push BS3 one time to access the
selected setting's value.
To quit and return to the
Push BS1.
initial status
Changing the value of the
▪ Push BS1 for more than five seconds
selected setting in mode 2
to select mode 2.
▪ Push BS2 to select the required
setting.
▪ Push BS3 one time to access the
selected setting's value.
▪ Push BS2 to select the required value
of the selected setting.
▪ Push BS3 one time to validate the
change.
▪ Push BS3 again to start operation
with the chosen value.
18.1.6

Mode 1: monitoring settings

[1‑1]
Shows the status of low noise operation.
[1‑1]
0
Unit is currently not operating under low noise
restrictions.
1
Unit is currently operating under low noise
restrictions.
18 Configuration
Action
"18.1.3 To access mode 1
How
Push BS1 one time to select
mode 1.
Push BS2 to select the required
setting.
Push BS3 one time to access the
selected setting's value.
How
Description
Installation and operation manual