Engineers set class, non-personnel do not arbitrarily enter the change,
*
in order to avoid abnormal。
INPUT Group
Operation display
Press
Key Enter the setup menus
Password
0000 9999
▼KEY
~
Default 1000
A 1 -
Voltage Phase line set
Set range is as follows:
1P2W/1P3W/3P3W/
3P3W.B(Balanced)/3P3W3/
3P4W/3P4W.B (Balanced)
Default:3P4W
A 2 -
Primary voltage (PT)
Set range:100~500000V
Default 600
A 3 -
Secondary voltage
Set range 100~600V
:
Default:
A 4 -
Primary current (CT)
Set range 5~10000A
:
Default 5 :
:
:
(PT)
600
9
A 5 -
Watt-h / Var Clear
Clear Passwords:
~
0000 9999
Code:2100
A-6
P.COD
Set range:
~
0000 9999
:
Default 1000
A 7 -
Auto wiring change
◎Additional screen display
for V3.0 and above version
YES / NO
Rs485 Group
E-1
Communication
station No.
Set range:001~247
Default 1 :
E 2 -
Communications
transmission rate
Set range:
1200 2400
、
、4800、9600、
19200、38400
Default 6
:9 00
Need help?
Do you have a question about the CPM-21 and is the answer not in the manual?
Questions and answers