Modbus Server – DALI
TM
Intesis
If too many ECGs have been instantiated, they can be deleted by selecting them, and pressing button 'Delete
ECG(s)'. Multiple selection is also possible.
Finally, for all ballasts in configuration, you will need to define:
-
ECG Name (optional): Name to ease its identification in the network
Device type: It's important that this field is suitably chosen and according to existing ballast in the
-
network (device type 0: Fluorescent Light, device type 1: Emergency Light, device type 6: LED module
or 'Other' (default) if none of the above matches the device type).
-
Commitable ECG Parameters: This includes all preset values for the ballasts (min level, max level,
power on level, etc), as well as group assignation and scene configuration.

Scan and commissioning of ECGs

First you need to get MAPS connected to the Intesis device. To do so, go to 'Connection' tab of MAPS. There, select
appropriate connection mode (IP or USB). Select your device from the list of scanned devices (IP) or suitable COM
port (USB).
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
A.4
Figure
Deleting DALI ECGs
A.5
Figure
Connecting MAPS to the Intesis
User Manual r1.3 EN