HMS Networks Intesis INMBSDAL0640000 User Manual page 10

Modbus server digitally addressable lighting interface (dali)
Table of Contents

Advertisement

Modbus Server – DALI
TM
Intesis
Ballast /
Device type
Modbus Address
First Address is 0
7000 x channel + (100 x sa)
x
+ 3
7000 x channel + (100 x sa)
x
+ 4
7000 x channel + (100 x sa)
x
+ 5
7000 x channel + (100 x sa)
x
+ 6
7000 x channel + (100 x sa)
x
+ 7
7000 x channel + (100 x sa)
x
+ 8
7000 x channel + (100 x sa)
x
+ 9
7000 x channel + (100 x sa)
x
+ 10
7000 x channel + (100 x sa)
x
+ 11
7000 x channel + (100 x sa)
x
+ 12
7000 x channel + (100 x sa)
x
+ 13
7000 x channel + (100 x sa)
x
+ 14
7000 x channel + (100 x sa)
x
+ 15
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
Read/
Register/signal name
Write
Ballast / Lamp Failure bit fields
x
x
R
(ECG63-ECG48)
x
x
R/W
Update All ECG Status
x
x
R
Ballast Status
x
x
R
Actual Level
x
x
R
Device Type
x
x
R
Physical Minimum Level
x
x
R
Min Level
x
x
R
Max Level
x
x
R
Power On Level
x
x
R
System Failure Level
x
x
R
Fade Time
x
x
R
Fade Rate
x
x
R/W
Arc Power Level
Possible values
0-OK, 1-Ballast / Lamp Failure bi [i = sa - (16 * (line-1))]
0-Update Finished, 1-Trigger Update
b7-PwrCycle, b6-MissShAdd, b5-ResetSt, b4-FadeRun,
b3-BallLimErr, b2-LampPwrOn, b1-LampFail, b0-BallFail
0 to 100 %
0-Fluorescent, 1-Emergency, 2 Discharge, 3-Halogen, 4-
Incandescent, 5-Digital signal, 6-LED, 7-Switching, 8-
Colour Control
0 to 100 %
0 to 100 %
0 to 100 %
0 to 100 %
0 to 100 %
0 to 15
1 to 15
0 to 100 %
User Manual r1.3 EN