HMS Networks Intesis INMBSDAL0640000 User Manual page 11

Modbus server digitally addressable lighting interface (dali)
Table of Contents

Advertisement

Modbus Server – DALI
TM
Intesis
Ballast /
Device type
Modbus Address
First Address is 0
7000 x channel + (100 x sa)
x
+ 16
7000 x channel + (100 x sa)
x
+ 17
7000 x channel + (100 x sa)
x
+ 18
7000 x channel + (100 x sa)
x
+ 19
7000 x channel + (100 x sa)
x
+ 20
7000 x channel + (100 x sa)
x
+ 21
7000 x channel + (100 x sa)
x
+ 22
7000 x channel + (100 x sa)
x
+ 23
7000 x channel + (100 x sa)
x
+ 24
7000 x channel + (100 x sa)
x
+ 25
7000 x channel + (100 x sa)
x
+ 26
7000 x channel + (100 x sa)
x
+ 27
7000 x channel + (100 x sa)
x
+ 28
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
Read/
Register/signal name
Write
x
x
R/W
Arc Power Off / On
x
x
R/W
Step Down / Up
W
x
x
(trigge
Recall Min Level
r)
W
x
x
(trigge
Recall Max Level
r)
x
x
R/W
Go to Scene
x
x
R/W
Store Current Level as Scene
x
x
R/W
Clear/Remove Scene
x
x
R/W
Set Fade Time
x
x
R/W
Set Fade Rate
x
x
R/W
Set Min Level
x
x
R/W
Set Max Level
x
x
R/W
Set Power-on Level
x
x
R/W
Set System-failure Level
Possible values
0-Off; 1-100 %
0-Step Down, 1-Step Up
1-Recall Min Level
1-Recall Max Level
0 to 15
0 to 15
0 to 15
0 to 15
1 to 15
0 to 100 %
0 to 100 %
0 to 100 %
0 to 100 %