HMS Networks Intesis INMBSDAL0640000 User Manual page 15

Modbus server digitally addressable lighting interface (dali)
Table of Contents

Advertisement

Modbus Server – DALI
TM
Intesis
Ballast /
Device type
Modbus Address
First Address is 0
7000 x channel + (100 x sa)
+ 67
7000 x channel + (100 x sa)
+ 68
7000 x channel + (100 x sa)
+ 69
7000 x channel + (100 x sa)
+ 70
7000 x channel + (100 x sa)
+ 71
7000 x channel + (100 x sa)
+ 72
7000 x channel + (100 x sa)
+ 73
7000 x channel + (100 x sa)
+ 74
7000 x channel + (100 x sa)
+ 75
7000 x channel + (100 x sa)
+ 76
7000 x channel + (100 x sa)
+ 77
7000 x channel + (100 x sa)
+ 78
7000 x channel + (100 x sa)
+ 79
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
Read/
Register/signal name
Write
x
W
Reset Duration Test Done Flag
x
W
Reset Lamp Time
x
R/W
Store Test Execution Timeout
x
R/W
Store Prolong Time
x
R/W
Store Function Test Interval
x
R/W
Store Duration Test Interval
x
R/W
Store Emergency Level
R
Not used
R
Not used
R
Not used
R
Not used
R
Not used
R
Not used
Possible values
1-Reset Duration Flag
1-Lamp Emergency Time Reset
0 to 255 days
0 to 127,5 minutes
0-Disabled, 1 to 255 days
0-Disabled, 1 to 97 weeks
0 to 100 %
Default to 0
Default to 0
Default to 0
Default to 0
Default to 0
Default to 0
User Manual r1.3 EN