HMS Networks Intesis INMBSDAL0640000 User Manual page 13

Modbus server digitally addressable lighting interface (dali)
Table of Contents

Advertisement

Modbus Server – DALI
TM
Intesis
Ballast /
Device type
Modbus Address
First Address is 0
7000 x channel + (100 x sa)
+ 42
7000 x channel + (100 x sa)
+ 43
7000 x channel + (100 x sa)
+ 44
7000 x channel + (100 x sa)
+ 45
7000 x channel + (100 x sa)
+ 46
7000 x channel + (100 x sa)
+ 47
7000 x channel + (100 x sa)
+ 48
7000 x channel + (100 x sa)
+ 49
7000 x channel + (100 x sa)
+ 50
7000 x channel + (100 x sa)
+ 51
7000 x channel + (100 x sa)
+ 52
7000 x channel + (100 x sa)
+ 53
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
Read/
Register/signal name
Write
x
R
Failure Status
x
R
Emergency Mode
x
R
Emergency Status
x
R
Emergency Battery Charge
x
R
Next Function Test
x
R
Next Duration Test
x
R
Function Test Interval
x
R
Duration Test Interval
x
R
Test Execution Timeout
x
R
Prolong Time
x
R
Duration Test Result
x
R
Lamp Total Operation Time
Possible values
b7-FunctFail, b6-DurFail, b5-DurTestDelay, b4-
FunctTestDelay, b3-EmLampFail, b2-BattFail, b1-
BattDurFail, b0-CircFail
b7-HardSwOn, b6-HardInhibit, b5-DurTestProg, b4-
FunctTestProg, b3-ExtdEmMode, b2-EmMode, b1-
NormMode, b0-RestMode
b7-PhysicSel, b6-Ident, b5-DurTestPend, b4-
FunctTestPend, b3-BattFull, b2-DurTestDone, b1-
FunctTestDone, b0-InhibitMode
0 to 100 %
0 to 16384 hours
0 to 16384 hours
0-Disabled, 1 to 255 days
0-Disabled, 1 to 97 weeks
0 to 255 days
0 to 127,5 minutes
0 to 510 minutes
0 to 1016 hours
User Manual r1.3 EN
URL
https://www.intesis.com
13 / 39