HMS Networks Intesis INMBSDAL0640000 User Manual page 14

Modbus server digitally addressable lighting interface (dali)
Table of Contents

Advertisement

Modbus Server – DALI
TM
Intesis
Ballast /
Device type
Modbus Address
First Address is 0
7000 x channel + (100 x sa)
+ 54
7000 x channel + (100 x sa)
+ 55
7000 x channel + (100 x sa)
+ 56
7000 x channel + (100 x sa)
+ 57
7000 x channel + (100 x sa)
+ 58
7000 x channel + (100 x sa)
+ 59
7000 x channel + (100 x sa)
+ 60
7000 x channel + (100 x sa)
+ 61
7000 x channel + (100 x sa)
+ 62
7000 x channel + (100 x sa)
+ 63
7000 x channel + (100 x sa)
+ 64
7000 x channel + (100 x sa)
+ 65
7000 x channel + (100 x sa)
+ 66
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
Read/
Register/signal name
Write
x
R
Emergency Level
x
R
Emergency Min Level
x
R
Emergency Max Level
x
R
Rated Duration
x
R
Features
x
R
Lamp Emergency Time
x
W
Rest
x
W
Inhibit
x
W
Re-Light/Reset Inhibit
x
W
Start Function Test
x
W
Start Duration Test
x
W
Stop Test
x
W
Reset Function Test Done Flag
Possible values
0 to 100 %
0 to 100 %
0 to 100 %
0 to 510 minutes
b7-RelightRestSup, b6-PhysicSelSup, b5-HardInSup, b4-
AdjsEmLvl, b3-AutoTestCap, b2-SwitchMainCG, b1-
MainCG, b0-IntegralEmCG
0 to 254 hours
1-Extinguish Lamp
1-Start Inhibit mode
1-Cancel Inhibit Mode
1-Start Function Test
1-Start Duration Test
1-Stop Function/Duration Test
1-Reset Function Flag
User Manual r1.3 EN
URL
https://www.intesis.com
14 / 39