Modbus Server – DALI
TM
Intesis

Set-up procedure

1. Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by
the Installation wizard.
2. Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface
(DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended).
3. If using Modbus RTU, connect the communication cable coming from the EIA485 port of the Modbus RTU
installation to the port marked as Port B of Intesis (More details in section 3).
If using, Modbus TCP, connect the communication cable coming from the Ethernet port of the Modbus TCP
installation to the port marked as Ethernet Port of Intesis (More details in section 3).
4. Connect the communication cable coming from DALI network to the port marked as Port A of Intesis (More details
in section 3).
5. If using two DALI channels, connect communication cable coming from second DALI network to the port marked
as Port B of Intesis (More details in section 3).
6. Power up Intesis. The supply voltage should be any of the voltage range allowed (check section 5).. Take care
of the polarity of the supply voltage applied.
WARNING! In order to avoid earth loops that can damage Intesis and/or any other equipment connected to
it, we strongly recommend the use of DC power supplies, floating or with the negative terminal connected to
earth. Never use a DC power supply with the positive terminal connected to earth.
7. If you want to connect using IP, connect the Ethernet cable from the laptop PC to the port marked as Ethernet of
Intesis (More details in section 3).
If you want to connect using USB, connect the USB cable from the laptop PC to the port marked as Console of
Intesis (More details in section 3).
8. Open Intesis MAPS, create a new project for Modbus and select the INMBSDAL---0000-Template project.
9. Modify the configuration as desired, save it and download the configuration file to Intesis as explained in section
4.2.5 .
10. Visit the Diagnostic section, enable COMMS and check that there is communication activity, some TX frames
and some other RX frames. This means that the communication with the Centralized Controller and Modbus
Master devices is OK. In case there is no communication activity between Intesis and the Centralized Controller
and/or Modbus devices, check that those are operative: check the baud rate, the communication cable used to
connect all devices and any other communication parameter.