9.2.4 To connect the user interface

EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
3 Fix the cable with cable ties to the cable tie mountings.
This topic describes the following:
Connecting the user interface cable to the outdoor unit.
Installing the user interface, and connecting the user interface cable to it.
(if necessary) Opening the user interface after it is installed.
Connecting the user interface cable to the outdoor unit
Wires: 4×(0.75~1.25 mm²)
Maximum length: 200 m
[2.9] Control
[1.6] Room sensor offset
1 Open the service cover. See
2 Connect the user interface cable to the outdoor unit. Fix the cable with cable
ties to the cable tie mountings.
a User interface: Required for operation. Delivered with the unit as accessory.
X2M
"To open the outdoor
a
X1B
X5M.11
4
X5M.12
3
X5M.16
2
X5M.15
1
9
Electrical installation
|
4
unit" [
 61].
P1P2
+
PSU
Installer reference guide