9.2.4 To connect the user interface
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
3 Fix the cable with cable ties to the cable tie mountings.
This topic describes the following:
▪
Connecting the user interface cable to the outdoor unit.
▪
Installing the user interface, and connecting the user interface cable to it.
▪
(if necessary) Opening the user interface after it is installed.
Connecting the user interface cable to the outdoor unit
Wires: 4×(0.75~1.25 mm²)
Maximum length: 200 m
[2.9] Control
[1.6] Room sensor offset
1 Open the service cover. See
2 Connect the user interface cable to the outdoor unit. Fix the cable with cable
ties to the cable tie mountings.
a User interface: Required for operation. Delivered with the unit as accessory.
X2M
"To open the outdoor
a
X1B
X5M.11
4
X5M.12
3
X5M.16
2
X5M.15
1
9
Electrical installation
|
4
unit" [
61].
P1P2
+
PSU
Installer reference guide
91