Daikin EWAA0 DAV3P Series Installer's Reference Manual page 177

Packaged air-cooled water chillers and packaged air to water heat pumps
Table of Contents

Advertisement

Alarm output
Auto restart
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
#
Code
[7.5.2]
N/A
[7.5.3]
N/A
[7.6]
N/A
Alarm output
#
Code
[9.D]
[C–09]
Alarm output logic
[C-09]
0
Closed output
1
Open output
Auto restart
When power returns after a power supply failure, the auto restart function
reapplies the user interface settings at the time of the power failure. Therefore, it
is recommended to always enable the function.
If the preferential kWh rate power supply is of the type that power supply is
interrupted, always enable the auto restart function. Continuous hydro module
control can be guaranteed independent of the preferential kWh rate power supply
status, by connecting the hydro module to a separate normal kWh rate power
supply.
#
Code
[9.E]
[3-00]
User settings > Electricity price >
Medium
User settings > Electricity price >
Low
User settings > Gas price
Alarm output: Indicates the logic of the alarm
output on the digital I/O PCB during
malfunctioning.
0 Abnormal: The alarm output will be
powered when an alarm occurs. By setting this
value, a distinction is made between the
detection of an alarm, and the detection of a
power failure.
1 Normal: The alarm output will NOT be
powered when an alarm occurs.
See also table below (Alarm output logic).
Alarm
No alarm
Open output
Closed output
Auto restart:
0: Manual
1: Automatic
11
Configuration
|
Description
Description
No power supply
to unit
Open output
Description
Installer reference guide
177