14.2.2 Yearly maintenance outdoor unit: instructions

EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to dust, dirt,
leaves, etc. It is recommended to clean the heat exchanger yearly. A blocked heat
exchanger can lead to too low pressure or too high pressure leading to worse
performance.
Water filter
Close the valve. Clean and rinse the water filter.
NOTICE
Handle the filter with care. To prevent damage to the mesh of the filter, do NOT use
excessive force when you reinsert it.
2
1
3
Water pressure
Keep water pressure above 1 bar. If it is lower, add water.
Water pressure relief valve
Open the valve and check if it operates correctly. The water may be very hot!
Checkpoints are:
The water flow coming from the relief valve is high enough, no blockage of the
valve or in between piping is suspected.
Dirty water coming out of the relief valve:
-
open the valve until the discharged water does NOT contain dirt anymore
-
flush the system
It is recommended to do this maintenance more frequently.
Switch box
Carry out a thorough visual inspection of the switch  box and look for obvious
defects such as loose connections or defective wiring.
Using an ohmmeter, check if contactors K1M, K2M, K3M and K5M (depending on
your installation) operate correctly. All contacts of these contactors must be in
open position when the power is turned OFF.
WARNING
If the internal wiring is damaged, it has to be replaced by the manufacturer, its
service agent or similarly qualified persons.