Field settings table
Breadcrumb Field code
Setting name
9.I
[C-02]
Is an external backup heat source connected?
9.I
[C-03]
Bivalent activation temperature.
9.I
[C-04]
Bivalent hysteresis temperature.
9.I
[C-05]
What is the thermo request contact type for the main zone?
9.I
[C-06]
What is the thermo request contact type for the add. zone?
9.I
[C-07]
What is the unit control method in space operation?
9.I
[C-08]
Which type of external sensor is installed?
9.I
[C-09]
What is the required alarm output contact type?
9.I
[C-0A]
--
9.I
[C-0B]
--
9.I
[C-0C]
--
9.I
[C-0D]
--
9.I
[C-0E]
--
9.I
[D-00]
Which heaters are permitted if prefer. kWh rate PS is cut?
9.I
[D-01]
Contact type of preferential kWh rate PS installation?
9.I
[D-02]
Which type of DHW pump is installed?
9.I
[D-03]
Leaving water temperature compensation around 0°C.
9.I
[D-04]
Is a demand PCB connected?
9.I
[D-05]
Is the pump allowed to run if prefer. kWh rate PS is cut?
9.I
[D-07]
Is a solar kit connected?
9.I
[D-08]
Is an external kWh meter used for power measurement?
9.I
[D-09]
Is an external kWh meter used for power measurement, kWh meter used for smart
grid or a gas meter for hybrid unit?
9.I
[D-0B]
--
9.I
[D-0C]
--
9.I
[D-0D]
--
9.I
[D-0E]
--
9.I
[E-00]
Which type of unit is installed?
9.I
[E-01]
Which type of compressor is installed?
9.I
[E-02]
What is the indoor unit software type?
9.I
[E-03]
What is the number of backup heater steps?
9.I
[E-04]
Is the power saving function available on the outdoor unit?
9.I
[E-05]
Can the system prepare domestic hot water?
9.I
[E-06]
Is a DHW tank installed in the system?
9.I
[E-07]
What kind of DHW tank is installed?
9.I
[E-08]
Power saving function for outdoor unit.
9.I
[E-09]
--
9.I
[E-0B]
Is a bi-zone kit installed?
9.I
[E-0C]
--
9.I
[E-0D]
Is glycol present in the system?
9.I
[E-0E]
--
9.I
[F-00]
Pump operation allowed outside range.
9.I
[F-01]
Above which outdoor temperature is cooling allowed?
9.I
[F-02]
Bottom plate heater ON temperature.
9.I
[F-03]
Bottom plate heater hysteresis.
9.I
[F-04]
Is a bottom plate heater connected?
(*1) EWAA*
(*2) EWYA*
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/O
R/W (*2)
R/O (*1)
R/W
R/O
R/W
R/O
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
(#) Setting is not applicable for this unit.
Range, step
Default value
0: No
1: Bivalent
-25~25°C, step: 1°C
0°C
2~10°C, step 1°C
3°C
0: -
1: 1 contact
2: 2 contacts
0: -
1: 1 contact
2: 2 contacts
0: LWT control
1: Ext RT control
2: RT control
0: No
1: Outdoor sensor
2: Room sensor
0: Normally open
1: Normally closed
0
0
0
0
0
0: None
1: BSH only
2: BUH only
3: All heaters
0: No
1: Active open
2: Active closed
3: Smart grid
0: No
1: Secondary rtrn
2: Disinf. Shunt
3: Circulation Pump
4: Circulation Pump and disinf. Shunt
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
0: No
1: Pwr consmp ctrl
0: Forced off
1: As normal
0: No
1: Yes
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
8: 1 pulse/m³ (gas meter)
9: 10 pulses/m³ (gas meter)
10: 100 pulses/m³ (gas meter)
2
0
0
0
0~5
1:Mini chiller
1
0: Reversible (*2)
1: Cooling only (*1)
0: no BUH
1: External BUH
0: No
1: Yes
0: No
1: Yes
0: No
1: Yes
0~6
1: EKHW
5: EKHWP
0: Disabled
1: Enabled
1
0
0
0: No
1: Yes
0
0: Disabled
1: Enabled
10~35°C, step: 1°C
20°C
3~10°C, step: 1°C
3°C
2~5°C, step: 1°C
5°C
0
9/10
Installer setting at variance with
default value
Date
Value