Daikin EWAA0 DAV3P Series Installer's Reference Manual page 31

Packaged air-cooled water chillers and packaged air to water heat pumps
Table of Contents

Advertisement

Fan coil units
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
Setup
A Main leaving water temperature zone
B One single room
a User interface (delivered as accessory)
b Remote controller of the fan coil units
For more information about connecting the electrical wiring to the unit, see
"9.2 Connections to the outdoor
The fan coil units are directly connected to the outdoor unit – or to the external
backup heater kit, if there is one.
The desired room temperature is set via the remote controller of the fan coil
units.
The space heating/cooling demand signal is sent to one digital input on the
outdoor unit (X2M/35 and X2M/30).
The space operation mode is sent to the fan coil units by one digital output on
the outdoor unit (X2M/4 and X2M/3).
INFORMATION
When using multiple fan coil units, make sure each one receives the infrared signal
from the remote controller of the fan coil units.
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
Number of water temperature zones:
#: [4.4]
Code: [7-02]
External room thermostat for the main
zone:
#: [2.A]
Code: [C-05]
Benefits
Cooling. The fan coil unit offers, besides heating capacity, also excellent cooling
capacity.
Efficiency. Optimal energy efficiency because of the interlink function.
B
A
a
b
4
unit" [
 78].
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or fan coil
unit can only send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
6
Application guidelines
|
Value
Installer reference guide
31