Daikin EWAA0 DAV3P Series Installer's Reference Manual page 214

Packaged air-cooled water chillers and packaged air to water heat pumps
Table of Contents

Advertisement

16
|
Disposal
Installer reference guide
214
#
Action
8
Press BS1 once.
H1P keeps flashing, indicating that
you are in a mode that does not
allow compressor operation.
(a)
= OFF,
= ON, and
Result: The recovery mode is activated. The unit opens the electronic expansion
valves.
To deactivate the recovery mode
After recovering refrigerant, deactivate the recovery mode as follows:
#
Procedure
1
Press and hold BS1 for 5 seconds.
2
Press BS2 9 times.
3
Press BS3 once.
4
Press BS2 once.
5
Press BS3 once.
6
Press BS3 once.
7
Press BS1 once to return to the
default situation.
(a)
= OFF,
= ON, and
Result: The recovery mode is deactivated. The unit returns the electronic
expansion valves to their initial state.
INFORMATION
Power OFF. When power is turned OFF and turned ON again, the recovery mode is
deactivated automatically.
H1P H2P H3P H4P H5P H6P H7P
= flashing.
H1P H2P H3P H4P H5P H6P H7P
= flashing.
(a)
7-LEDs display
(a)
7-LEDs display
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06