To determine if a heating/cooling heat pump model is installed
1 Go to [4]: Space heating/cooling.
2 Check if [4.1] Operation mode is listed and editable. If so, a
heating/cooling heat pump model is installed.
To tell the system which space operation to use, you can:
You can...
Check which space operation mode is currently used. Home screen
Set the space operation mode permanently.
Restrict automatic changeover according to a monthly
schedule.
To check which space operation mode is currently used
The space operation mode is displayed on the home screen:
When the unit is in heating mode, the
When the unit is in cooling mode, the
The status indicator shows if the unit is currently in operation:
When the unit is not in operation, the status indicator will show a blue pulsation
with an interval of approximately 5 seconds.
While the unit is in operation, the status indicator will light up blue constantly.
To set the space operation mode
1 Go to [4.1]: Space heating/cooling > Operation mode
2 Select one of the following options:
Heating: Only heating mode
Cooling: Only cooling mode
Automatic: The operation mode changes automatically
between heating and cooling based on the outdoor
temperature. Restricted per month according to the
Operation mode schedule [4.2].
Automatic heating/cooling changeover is only applicable for reversible models.
When Automatic is selected, the unit switches its operation mode, based on the
Operation mode schedule [4.2]. In this schedule, the end user indicates which
operation is allowed for each month.
To restrict automatic changeover according to a schedule
Conditions: You set the space operation mode to Automatic.
1 Go to [4.2]: Space heating/cooling > Operation mode
schedule.
2 Select a month.
3 For each month, select an option:
Reversible: Not restricted
Heating only: Restricted
Cooling only: Restricted
4 Confirm the changes.
Location
Main menu
icon is shown.
icon is shown.
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06