Daikin EWAA0 DAV3P Series Installer's Reference Manual page 139

Packaged air-cooled water chillers and packaged air to water heat pumps
Table of Contents

Advertisement

EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
#
Code
[2.7]
[2‑0C]
The setting Emitter type influences the space heating setpoint range and the
target delta T in heating as follows:
Emitter type Main
zone
0: Underfloor
heating
1: Fancoil unit
2: Radiator
NOTICE
The maximum setpoint in space heating depends on the emitter type as can be seen
in above table. If there are 2 water temperature zones, then the maximum setpoint
is the maximum of the 2 zones.
NOTICE
NOT configuring the system in the following way can cause damage to the heat
emitters. If there are 2 zones, it is important that in heating:
the zone with the lowest water temperature is configured as the main zone, and
the zone with the highest water temperature is configured as the additional zone.
NOTICE
If there are 2 zones and the emitter types are wrongly configured, water of high
temperature can be sent towards a low temperature emitter (underfloor heating). To
avoid this:
Install an aquastat/thermostatic valve to avoid too high temperatures towards a
low temperature emitter.
Make sure you set the emitter types for the main zone [2.7] and for the
additional zone [3.7] correctly in accordance with the connected emitter.
NOTICE
Average emitter temperature = Leaving water temperature – (Delta T)/2
This means that for a same leaving water temperature setpoint, the average emitter
temperature of radiators is lower than that of underfloor heating because of a bigger
delta T.
Example radiators: 40–8/2=36°C
Example underfloor heating: 40–5/2=37.5°C
To compensate, you can:
Increase the weather-dependent curve desired temperatures [2.5].
Enable leaving water temperature modulation and increase the maximum
modulation [2.C].
Emitter type:
0: Underfloor heating
1: Fancoil unit
2: Radiator
Space heating setpoint
range [9‑01]~[9‑00]
Maximum 55°C
Maximum 55°C
Maximum 60°C
11
Configuration
|
Description
Target delta T in heating
[1‑0B]
Variable (see [2.B.1])
Variable (see [2.B.1])
Fixed 8°C
Installer reference guide
139