Electricity meter ............26 ▪ Safety instructions that you must read before installing 5.15.5 Solar inverter/energy management system ....26 ▪ Format: Paper (in the box of the unit) 6 Configuration Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). 1× 4×...
The appliance shall be stored so as to prevent mechanical T-piece 22 mm×22 mm×22 mm damage and in a well-ventilated room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater). Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
3 Unit installation WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. Opening and closing the unit 3.2.1 To open the indoor unit NOTICE For a standard installation, it is usually NOT required to open the unit.
Pipes for central water loop circuit Pipes for space heating/cooling circuit 4 Uncouple the piping. 4× 4× 5 Remove the lower hydro module cover. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Page 9
4 8].) remove the hydro module from the 4 Drain remaining water from the hydro module. 8 Remove the screw that fixes the hydro module to the bottom plate. 1× EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
(overview field setting [9‑04]) is 4°C, the minimum water volume can be lowered to 10 litre. INFORMATION 1° 1° In critical processes, or in rooms with a high heat load, 0° extra water might be required. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
In this case, it is the responsibility of the installer to install a filter on the central water loop side of the system. EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Expansion vessel. An expansion vessel (field supply) MUST be installed on the entering piping before the water pump within 10 m of the unit. NOTICE Install air purge valves at all local high points. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Fixed grating Trapped gully Metal discharge pipe from safety device to tundish Discharge pipe from tundish, with continuous fall. See Building Regulation G3 section 3.56, Table 03 and worked example. EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Consider that the space heating piping can condensate during cooling operation. Foresee adequate insulation for these pipes. Remote outdoor "5.4 To connect the remote outdoor sensor" [ 4 18]. sensor Shut-off valve "5.5 To connect the shut-off valve" [ 4 18]. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Wires: 4×0.75 mm² Maximum running current: 100 mA For the main zone: ▪ [2.9] Control ▪ [2.A] Thermostat type For the additional zone: ▪ [3.A] Thermostat type ▪ [3.9] (read-only) Control EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Page 16
C2: Preferential kWh rate power supply contact C3: Separate normal kWh rate power supply for the hydro (1N~) C4: Connection of X11Y C5: Preferential kWh rate power supply for the compressor (1N~) Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Page 17
Preferential kWh rate power supply contact: 16 V DC detection (voltage supplied by PCB). The voltage-free contact shall ensure the minimum applicable load of 15 V DC, 10 mA. Connect the preferential kWh rate power supply contact (S1S) as follows. 1× EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
The positive polarity MUST be connected to X5M/6 and X5M/4; the negative polarity to X5M/5 and X5M/3. 1 Open the following (see "3.2.1 To open the indoor unit" [ 4 7]): EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
To connect the space cooling/ Cable sleeve (field supply) heating ON/OFF output Wires: (2+1)×0.75 mm² Maximum load: 3.5 A, 250 V AC — unit" [ 4 7]): 1 Open the following (see "3.2.1 To open the indoor Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
2 User interface panel 3 Front panel 4 Main switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
2 Connect the safety thermostat (normally closed) cable to the appropriate terminals as shown in the illustration below. 2 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
On the user interface, make sure to set BRP069A61), which allows for: [2.9]=2 (Control = Room thermostat) ▪ App control of the heat pump system ▪ Integration of the heat pump system in a Smart Grid application Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
It is recommended to connect the LAN adapter to the energy application router directly. Depending on the wireless bridge or power management line adapter model, the system might not function properly. system + 230 V AC detection voltage (X1A) EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
The rest of the wiring to X1A differs depending on the digital outputs available on the solar inverter/energy management system and/or on the Smart Grid operation modes that you want the system to run in. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
▪ Afterwards. If necessary, you can make changes to the solar inverter/energy management system to LAN adapter configuration in the menu structure or the overview settings. digital inputs X1A/1+2 LAN. EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
You can change all these settings via the menu structure. User pin code Protective functions The User pin code is 0000. The unit is equipped with the following protective functions: Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
To manually recover it via the user interface, go to the a Main LWT zone Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not. EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
The backup heater is adapted to be connected to most common European electricity grids. The type of backup heater can be viewed but not changed. Code Description [9.3.1] [E‑03] ▪ 4: 9W Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
For more info about this functionality, see "6.2.5 Configuration zone" [ 4 30]. wizard: Main To set the heat pump ON hysteresis: Code Description [5.9] [6-00] Heat pump ON hysteresis ▪ 2°C~40°C EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Because it reacts more quickly, it prevents high rises and drops of the indoor temperature and water temperature at tap points. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Main zone – Heating [2.4] Main zone > Setpoint WD heating, fixed cooling mode OR Weather dependent Main zone – Cooling [2.4] Main zone > Setpoint Weather dependent mode Additional zone – Heating EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
The installer can fill in his contact number here. The following table describes how to fine-tune the weather- Code Description dependent curve of a zone or tank: [8.3] Number that users can call in case of problems. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
[9.B] Sensors External sensor Ext. amb. sensor offset Averaging time [9.C] Bivalent Bivalent Boiler efficiency Temperature Hysteresis INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
▪ Between the indoor unit and the valves (if applicable) ▪ Between the indoor unit and the room thermostat (if applicable) The system is properly earthed and the earth terminals are tightened. EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
4 28]. change the user permission 2 Select OK to confirm. 2 Go to [A.2]: Commissioning > Actuator test run. 3 Select a test from the list. Example: Pump. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
4 10]. integral line strainer, pressure reducing valve cartridge and seating may be necessary. Fluid pressure Check whether the fluid pressure is above 1 bar. If it is lower, add fluid. Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Prerequisite: Open all the hot water tapping points to allow air to enter the system. Prerequisite: Remove the top panel. See "3.2.1 To open the indoor unit" [ 4 7]. 1 Remove the clip that fixes the domestic hot water OUT pipe. EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
4 Reinstall the clip to fix the domestic hot water OUT pipe. Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required).
PC=power circuit) (1) Main power connection (1) Main power connection Backup heater control PCB For preferential kWh rate power For preferential kWh rate power Inverter PCB supply supply * Demand PCB Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Page 45
Normally closed Normally open Normally open Safety thermostat contact: 16 V Safety thermostat contact: DC detection (voltage supplied 16 V DC detection (voltage by PCB) supplied by PCB) Shut-off valve Shut-off valve EWSAH/X06UDA9W Installation manual Daikin Altherma 3 WS 4P675760-1 – 2021.10...
Page 46
Power limitation demand input 3 FIELD SUPPLY A8P: X801M: 3-5 signal 2 core Power limitation demand input 4 Router for LAN adapter A8P: X801M: 4-5 A15P: X4A signal ethernet 4D137622 Installation manual EWSAH/X06UDA9W Daikin Altherma 3 WS 4P675760-1 – 2021.10...
WARNING TO INSTALLER ■ This installation is subject to building regulation approval, notify Local Authority of intention to install. ■ Use only manufacturer's recommended spare parts. Contact your local Daikin dealer. ■ Installed by name address tel. No.
Page 48