Daikin EWAA0 DAV3P Series Installer's Reference Manual page 127

Packaged air-cooled water chillers and packaged air to water heat pumps
Table of Contents

Advertisement

EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
a
Y4
Y3
Y2
Y1
X1
Weather-dependent curve when offset is selected:
a
Y4
Y3
Y2
Y1
Item
a
WD curve before changes.
b
WD curve after changes (as example):
When slope is changed, the new preferred temperature at X1 is
unequally higher than the preferred temperature at X2.
When offset is changed, the new preferred temperature at X1 is
equally higher as the preferred temperature at X2.
c
Slope
d
Offset
e
Selected weather dependent zone:
: Main zone or additional zone heating
: Main zone or additional zone cooling
X1, X2
Examples of outdoor ambient temperature
Y1, Y2, Y3,
Examples of desired leaving water temperature. The icon
Y4
corresponds to the heat emitter for that zone:
: Underfloor heating
: Fan coil unit
: Radiator
Select slope or offset.
Increase or decrease the slope/offset.
When slope is selected: set slope and go to offset.
When offset is selected: set offset.
Confirm changes and return to the submenu.
b
X2
b
X1
X2
Description
Possible actions on this screen
11
Configuration
|
c
e
d
c
e
d
Installer reference guide
127