3.3.3 Communication Characteristics
Communications Specifications:
Max. Communication
1200 m
Distance
Max. Connection
32
Number
Communication
MODBUS RTU
Protocols
03, 06, 10,
Function Code
FE (only available for
DPM-C502)
Use two-wire cables for RS-485 communication.
The D+ communication terminal for all devices should be connected on the same twisted pair cable. The
D- terminals should be connected on the other twisted pair cable. The insulation net is grounded. The
device on the end terminal needs to have terminal resistor installed on it.
Use cables with a diameter of 14 to 24 AWG.
C h a p t e r 3 I n s t a l l a t i o n
Baud Rate
9600, 19200, 38400
Data Length
8
Parity
None, Odd, Even
Stop Bit
1
3_
3 - 7
Need help?
Do you have a question about the DPM-C501L and is the answer not in the manual?
Questions and answers