5E
40095 Alarm Enable
5F
40096 Pickup setpoint (total active
power value exceeding this
60
40097
value; alarm triggered)
61
40098 Reserved
62
40099 Dropout setpoint (total
active power value below
63
40100
this value; alarm cleared)
64
40101 Reserved
65
40102 Alarm Enable
66
40103 Pickup setpoint (total
reactive power value
exceeding this value;alarm
67
40104
triggered)
68
40105 Reserved
69
40106 Dropout setpoint (total
reactive power value below
6A
40107
this value; alarm cleared)
6B
40108 Reserved
6C
40109 Alarm Enable
6D
40110 Pickup setpoint (total
apparent power value
6E
40111
exceeding this value; alarm
Ch ap te r 5 Para me ters a nd Func tio ns
Alarm - Over Active Power
0: Disable
1: Enable
0.000 - 99999.999
0.000 - 99999.999
Over Reactive Power
0: Disable
1: Enable
0.000 - 99999.999
0.000 - 99999.999
Alarm - Over Apparent Power
0: Disable
1: Enable
0.000 - 99999.999
word
2
R/W
float
kW
4
R/W
float
kW
4
R/W
word
2
R/W
float
kVAR
4
R/W
float
kVAR
4
R/W
word
2
R/W
float
kVA
4
R/W
5_
5_
5 - 7