3.3.2 Communication Characteristics

Communications Specifications:
Max. Communication
Distance
_3
_3
Max. Connection
Number
Communication
Protocols
Function Code
Note: The 7-bit data length is not available for the Modbus RTU protocol.
Use shielded twisted-pair cables for RS485 communication. When connecting multiple devices in series,
use the wiring method in the following diagram.
Connect the D+ communication terminal for all devices on the same twisted pair cable. Connect the D-
terminals on the other twisted pair cable. Ground the cable shield. Install a terminal resistor on the
terminal device as shown.
Use cables with a diameter of 14–28 AWG.
3 - 6
Current
Grounding
transformer
1200 m
32
Modbus RTU/ASCII,
BACnet MS/TP
03, 06, 10, FE
Ter minal Resistor
Terminal
Voltage
block
transformer
Baud Rate
9600, 19200, 38400 bps
Data Length
7-, 8-bits
Parity
None, Odd, Even
Stop Bits
1, 2
Fuse