Delta DPM-C530 Series Operation Manual

Delta DPM-C530 Series Operation Manual

Multi-functional power meter
Hide thumbs Also See for DPM-C530 Series:

Advertisement

Quick Links

Digitized Automation for a Changing World
Multi-functional Power Meter
DPM-C530 Series Operation Manual
www.deltaww.com

Advertisement

loading
Need help?

Need help?

Do you have a question about the DPM-C530 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Delta DPM-C530 Series

  • Page 1 Digitized Automation for a Changing World Multi-functional Power Meter DPM-C530 Series Operation Manual www.deltaww.com...
  • Page 2 Multi-functional Power Meter DPM-C530 Series Operation Manual Revision History Ve r s i o n R e v i s i o n D a t e T h e f i r s t v e r s i o n w a s p u b l i s h e d .
  • Page 3 Multi-functional Power Meter DPM-C530 Series Operation Manual Table of Contents Chapter 1 Product Introduction Preface ....................1-2 Overview ................... 1-2 Safety Precautions ................1-4 Chapter 2 Product Specifications Electrical Characteristics ..............2-2 Communications Specifications ............2-5 Operating the Display ................ 2-5 2.3.1...
  • Page 4 4.2.4 Ethernet Communication ..... 4-6 (Applicable only for DPM-C530E/C530EM) 4.2.5 Serial Master ......4-7 (Applicable only for DPM-C530E/C530EM) 4.2.6 IP Filter ........4-7 (Applicable only for DPM-C530E/C530EM) 4.2.7 Set up the Transformer Ratio ............4-8 4.2.8 Set up the System ..............4-9 4.2.9 Set up the Alarms ..............
  • Page 5 Chapter 5 Parameters and Funcitons Overview of Parameters ..............5-2 Modbus Communication ..............5-101 5.2.1 Supported Modbus Function Codes ..........5-101 5.2.2 Modbus Communication Protocol ..........5-101 5.2.3 Packet Format for Modbus Function Code 0xFE ......5-103 Chapter 6 Error Codes Error Codes ..................
  • Page 6 Chapter 1 Product Introduction Table of Contents Preface ....................1-2 Overview ................... 1-2 Safety Precautions ................1-4 1 - 1...
  • Page 7 If you still experience issues when using the device, please contact your distributor or our customer service center. As the product is updated and improved, changes to the specifications will be included in the newest version of the manual which you can get by contacting your distributor or downloading it from the Delta Electronics website (Delta | Download Center).
  • Page 8 Cha p ter 1 P r o d u c t I n t r o d u c t i o n The DPM-C530E/C530EM is equipped with a large, back-lit LCD display that displays up to four lines of information.
  • Page 9 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l Safety Precautions Installation Notes ...
  • Page 10 Chapter 2 Product Specifications Table of Contents Electrical Characteristics ..............2-2 Communications Specifications ............2-5 Operating the Display ................2-5 2.3.1 Menu Tree ..................2-7 Dimensions ..................2-10 2 - 1...
  • Page 11 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l Electrical Characteristics Measurement Accuracy ±...
  • Page 12 C h a p t e r 2 P r o d u c t S p e c i f i c a t i o n s Frequency Operating frequency 50/60 Hz Modbus-RTU, Modbus ASCII, BACnet MS/TP RS-485 port Baud rate 9600 / 19200 / 38400/ 76800 bps Communication Ethernet...
  • Page 13 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l 50 Ω...
  • Page 14 C h a p t e r 2 P r o d u c t S p e c i f i c a t i o n s Communications Specifications Communications (Applicable only for DPM-C530, DPM-C532/C532M) RS-485 Modbus-RTU, Modbus ASCII, BACnet MS/TP Baud rate 9600 / 19200 / 38400 / 76800 bps Communications (Applicable only for DPM-C530E/C530EM)
  • Page 15 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l *Home page display: Description Parameter...
  • Page 16 C h a p t e r 2 P r o d u c t S p e c i f i c a t i o n s 2.3.1 Menu Tree DPM-C530  2 - 7...
  • Page 17 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l DPM-C530E/C530EM ...
  • Page 18 C h a p t e r 2 P r o d u c t S p e c i f i c a t i o n s DPM-C532/C532M  2 - 9...
  • Page 19 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l Dimensions DPM-C530 Front ...
  • Page 20 C h a p t e r 2 P r o d u c t S p e c i f i c a t i o n s DPM-C530E/C530EM Front  Unit: mm (Inch) DPM-C530E/C530EM Back  2 - 11...
  • Page 21 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l DPM-C532/C532M Front ...
  • Page 22 Chapter 3 Installation Table of Contents Installation ..................3-2 3.1.1 Installation Environment ..............3-2 3.1.2 Installation Notes ................3-2 Basic Checks ..................3-4 Wiring ....................3-4 3.3.1 Wiring Diagrams ................3-4 3.3.2 Communication Characteristics............3-6 3.3.3 DI/ DO Wiring Diagram (Only applicable to DPM-C532/C532M) .... 3-7 3 - 1...
  • Page 23 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l Installation 3.1.1 Installation Environment...
  • Page 24 C h a p t e r 3 I n s t a l l a t i o n Step 2: Push the meter into the hole and then slide the securing bracket into the metal plate. Step 3: Allow 50 mm (2 inches) of clearance at the back of the meter for heat dissipation. Mounting Hole Dimensions ...
  • Page 25 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l Basic Checks Items Contents...
  • Page 26 C h a p t e r 3 I n s t a l l a t i o n Connection Diagrams 3PH3W, Δ connection, 3 CT, No PT 3PH3W, Δ connection, 2 CT, No PT 3PH3W, Δ connection, 3 CT, 2 PT 3PH4W, Y connection, 3 CT, No PT 3PH4W, Y connection, 3 CT, 3 PT 3PH4W, Y connection, 2 CT, 3 PT...
  • Page 27 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l The following table lists the symbols used in the diagram.
  • Page 28 C h a p t e r 3 I n s t a l l a t i o n Communications Specifications (DPM-C530E/C530EM):  Max. Communication Baud Rate 100 m 10/100Mbps Distance Communication MODBUS TCP Function Code 03, 06, 10, FE Protocols Topology Daisy Chain (without Ring topology)
  • Page 29 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l MEMO 3 - 8...
  • Page 30 Chapter 4 Operation Table of Contents General Operation ................4-3 4.1.1 Setting Menu ................4-3 Basic Setups ..................4-4 4.2.1 Set up the Time and Date ............... 4-4 4.2.2 Meter Information ................. 4-4 4.2.3 RS485 Communication ..4-5 (Applicable only for DPM-C530/DPM-C532/C532M) 4.2.4 Ethernet Communication ....
  • Page 31 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Power Analysis Values ..............4-23 4.4.1 Total Harmonic Distortion Measurement ......... 4-23 4.4.2 Demand Calculation Method ............4-23 Display with Decimal Places (Applicable only for DPM-C530 with firmware V 1.0406 .......................
  • Page 32 C h a p t e r 4 O p e r a t i o n 4.1 General Operation Use the UP and DOWN keys to switch among setting pages. Use the MENU key to go back to Menu page. Note 1: Use the ENTER key to enter a setting page and confirm the setting.
  • Page 33 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Basic Setups 4.2.1 Set up the Time and Date Time: Present power meter time; the time format includes the hour, minute, and second. ...
  • Page 34 C h a p t e r 4 O p e r a t i o n 4.2.3 RS485 Communication (Applicable only for DPM-C530/DPM-C532/C532M) Address (ID): Device ID; the address range is 1–254 (default: 1). 255 is the broadcast ID. ...
  • Page 35 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l 4.2.4 Ethernet Communication (Applicable only for DPM-C530E/C530EM) Address: Device ID; the address range is 1–254 (default: 1). 255 is the broadcast ID. ...
  • Page 36 C h a p t e r 4 O p e r a t i o n 4.2.5 Serial Master (Applicable only for DPM-C530E/C530EM) Config: Device ID; the options are Gateway and Monitor. The default is set to Gateway.  Protocol: Transmission modes;...
  • Page 37 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l 4.2.7 Set up the Transformer Ratio CT Primary: Primary-side current transformer amperes; 1–9999 A, 1 A is default. ...
  • Page 38 C h a p t e r 4 O p e r a t i o n 4.2.8 Set up the System Language: Language displayed on the power meter LCD; options are English (default), Japanese,  Simplified Chinese, and Traditional Chinese. Back Light: Brightness of the power meter LCD;...
  • Page 39 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l 4.2.9 Set up the Alarms There are 29 types of supported alarm, including Over Current, Under Current, Over Neutral Current, Over Voltage LL, Under Voltage LL, Over Voltage LN, Under Voltage LN, Over Volt Unbalance, Over AMP Unbalance, Over Active power, Over Reactive Power, Over Apparent Power, LEAD PF, Lag PF, Lead DPF, Lag DPF, Over Current Demand, Over kW Demand, Over kVAR Demand, Over kVA Demand, Over Frequency, Under...
  • Page 40 C h a p t e r 4 O p e r a t i o n 19. Select Time Delay and then press ENTER to set the alarm delay time (cancel). 20. After you select the target option, use UP and DOWN to select the value. 21.
  • Page 41 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l 4.2.11 Set up the Resets There are seven types of supported resets, including Default, Energy, Demand, Alarm, MaxMin, Data Log, and ClearAll.
  • Page 42 C h a p t e r 4 O p e r a t i o n 4.2.12 Digital Input Settings (Applicable only for DPM-C532/C532M) There are input filters and other three operation mode options for digital input settings. Input filters ...
  • Page 43 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l We suggest you set a proper filter time based on special values of input signals. Count would restart from 0 after reaching 999,999 and the count value would be saved in the FLASH every minute.
  • Page 44 C h a p t e r 4 O p e r a t i o n 4.2.13 Digital Output Settings (Applicable only for DPM-C532/C532M) There are four operation mode options for digital output settings. DI Control  You can map the state of any input port to its output status by configuring this output feature. Command ...
  • Page 45 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l 4.2.14 MID Lock (Applicable only for DPM-C532M/C530EM) To prevent parameters from being altered, when enabling MID Lock, the communication function will be set to read-only, and writing command is not allowed.
  • Page 46 C h a p t e r 4 O p e r a t i o n 4.3.2 Set up the Auto Recording Energy 1: Disable this function to restart auto-recording the group 1 energy value continuously; options  are Enable and Disable (default). Auto Day 1: Set the date to conclude the monthly accumulated energy value;...
  • Page 47 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l to cancel without saving the changes. Press MENU to go back to the setting menu. Example ...
  • Page 48 C h a p t e r 4 O p e r a t i o n 4.3.5 Set up the Groups Block transmission: Mirror the address of the to-be-read measured values to sequential Modbus  addresses. The mirrored addresses are 0x100–0x1E7. The default is 0xFFFF. Set up Steps ...
  • Page 49 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l 4.3.7 Tariff (Applicable only for DPM-C532 /C532M/DPM-C530E/C530EM) Different tariff schedules can be created based on dates and time periods of utility electricity consumption while different tariff energy value can be saved by using this tariff feature.
  • Page 50 C h a p t e r 4 O p e r a t i o n For more details, please refer to chapter 6 Error Codes. Schedule Example: In case that you want to create tariff rates for a duration from June 1st to September 30th, including an exceptional day August 15th, while time periods for workdays and holidays are different, the schedule would be like as the following shown.
  • Page 51 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Tariff of P7 Exceptional Days Enable function Enable Date August 15 Start & end time of P1~P8 DI control mode (Applicable only for DPM-C532/C532M) ...
  • Page 52 C h a p t e r 4 O p e r a t i o n Power Analysis Values 4.4.1 Total Harmonic Distortion Measurement The total harmonic distortion (THD) is a measurement of the harmonic distortion and is defined as the ratio between the power of the harmonic frequencies above the base frequency and the power of the base frequency.
  • Page 53 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Sliding window demand: The power meter provides measured values for current demand, active power ...
  • Page 54 C h a p t e r 4 O p e r a t i o n Switch Vavg Display on Homepage (Supported by firmware V 1.0410 or later in DPM-C530) Homepage Vavg display setting: Modify the Vavg display value featured with 1P3W or 3P4W wiring, ...
  • Page 55 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Network configuration: Network setup  Item Description IP mode Ethernet configuration IP address Internet protocol address Subnet mask Subnet mask Gateway...
  • Page 56 C h a p t e r 4 O p e r a t i o n Network configuration: Account management  Item Description User ID User account Password User password Access type User access privileges Network configuration: Firmware update ...
  • Page 57 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Current - Ic Phase C current value Current - Iavg Average current value Active Power - Total Value of total active power Active Power - Pa Value of phase A active power...
  • Page 58 C h a p t e r 4 O p e r a t i o n Data Monitor: Voltage  Item Description Voltage LN - Van Phase A voltage value Voltage LN - Vbn Phase B voltage value Voltage LN - Vcn Phase C voltage value Voltage LN - Vavg Average phase voltage value...
  • Page 59 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Data Monitor: Current  Item Description Current - Ia Phase A current value Current - Ib Phase B current value Current - Ic Phase C current value...
  • Page 60 C h a p t e r 4 O p e r a t i o n Apparent Power - Sa Value of phase A apparent power Apparent Power - Sb Value of phase B apparent power Apparent Power - Sc Value of phase C apparent power Data Monitor: Power Factor ...
  • Page 61 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Data Monitor: Energy  Item Description Active Energy - Delivered Positive active energy Active Energy - Received Negative active energy Reactive Energy - Delivered Positive reactive energy...
  • Page 62 C h a p t e r 4 O p e r a t i o n Data Monitor: Harmonic  Item Description THD of Current - Ia Value of phase A current harmonics THD of Current - Ib Value of phase B current harmonics THD of Current - Ic Value of phase C current harmonics THD of Voltage LN - Van...
  • Page 63 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Data Monitor: Demand  Item Description Current Demand - Present Value of the current demand for present Current Demand - Last Value of the previous current demand Current Demand - Predicted...
  • Page 64 C h a p t e r 4 O p e r a t i o n Apparent Power Demand - Peak Value of the peak reactive power demand Date of Apparent Power Demand Peak Peak reactive power demand date Time of Apparent Power Demand Peak Peak reactive power demand time Data Monitor: Maximum...
  • Page 65 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Time of Voltage LN - Vcn Time of max. phase C voltage Current- Ia The maximum phase A current value Date of - Ia Date of the max.
  • Page 66 C h a p t e r 4 O p e r a t i o n Data Monitor: Minimum  Item Description Voltage LL - Vab The minimum line AB voltage value Date of Voltage LL - Vab Date of min. line AB voltage Time of Voltage LL - Vab Time of min.
  • Page 67 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Current- Ib The minimum phase B current value Date of Current - Ib Date of the min. phase B current Time of Current - Ib Time of the min.
  • Page 68 C h a p t e r 4 O p e r a t i o n Data Monitor: Parameter grouping  Data Monitor: Alarm  Item Description Over Current Over current alarm Under Current Under current alarm Over Neutral Current Over neutral current alarm Over Voltage LL Over line voltage alarm...
  • Page 69 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Over Apparent Power Demand Over apparent power demand alarm Over Frequency Over frequency alarm Under Frequency Under frequency alarm Over THD of Voltage...
  • Page 70 C h a p t e r 4 O p e r a t i o n DPM configuration: Advanced configuration  Item Description Auto Metering #1 Auto metering #1 function switch Auto Metering #1 Day Auto metering #1 date setting Auto Metering #2 Auto metering #2 function switch Auto Metering #2 Day...
  • Page 71 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Save Config: Save configuration  After DPM configuration (Include: Basic and Advanced configuration) is completed, enter this page and press “Save”...
  • Page 72 C h a p t e r 4 O p e r a t i o n If you have not yet configured the account and password, enter the default (User: Admin) and press “Login”. After login successfully, the device tree would be displayed in the following area. 4 - 4 3...
  • Page 73 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l 4.7.3 Communication Card Firmware Update Steps are as follows:  Open the browser and connect to the power meter. Choose “Firmware update”...
  • Page 74 C h a p t e r 4 O p e r a t i o n Hit the Update button. Browse The update status shows “File upload processing”, which means the firmware of communication card is being updating. Browse Once the update status shows “Firmware update success”, the firmware updating task is completed.
  • Page 75 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l After reboot the power meter, connect to the webpage information: Check whether the firmware version in the Device Information is correct.
  • Page 76 Chapter 5 Parameters and Functions Table of Contents Overview of Parameters ..............5-2 Modbus Communication ..............5-101 5.2.1 Supported Modbus Function Codes ..........5-101 5.2.2 Modbus Communication Protocol ..........5-101 5.2.3 Packet Format for Modbus Function Code 0xFE ......5-103 5 - 1...
  • Page 77 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Overview of Parameters Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex)
  • Page 78 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0: 1 A Secondary CT(A) 1: 5 A word 000F 400016 2: 2.5 A...
  • Page 79 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Communication mode...
  • Page 80 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 7: Clear all values 8: Clear all tariffs and accumulated energy values of automatic metering.
  • Page 81 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0027...
  • Page 82 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 1: Enable 0035 400054 Pickup setpoint (That the line voltage 0.000 to 99999.999 Float 0036...
  • Page 83 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0043...
  • Page 84 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Alarm - Over Voltage Unbalance 0: Disable Alarm enables word 0050 400081...
  • Page 85 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) clears alarm.)
  • Page 86 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) (That the total reactive power value is below 006A 400107 this value clears alarm.)
  • Page 87 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Pickup time delay...
  • Page 88 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) displacement power factor value is below this value triggers alarm.) Pickup time delay 0 to 99...
  • Page 89 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) (Alarm-clear delay)
  • Page 90 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) below this value clears alarm.) Dropout time delay 0 to 99 word 009C 400157...
  • Page 91 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 00A8...
  • Page 92 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 00B6 400183 Dropout setpoint (When the frequency 0.0000 to 99.9999 Float value exceeds this 00B7...
  • Page 93 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) (That the THD current...
  • Page 94 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) (Alarm-trigger delay) 00D9 400218 Dropout setpoint (When the EUI value 0.000 to 99999.999 Float kWh / m2 00DA...
  • Page 95 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0105...
  • Page 96 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0125 400294 0126 400295 Three to phase 0.000 to 99999.999 Float average current 0127...
  • Page 97 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) factor of phase B...
  • Page 98 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0152 400339 Instantaneous -99999.999 to 99999.999 reactive power of (positive: lag;...
  • Page 99 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) to active energy of...
  • Page 100 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) voltage 017E 400383 Total harmonic distortion for phase B 0.000 to 999.999 Float 017F...
  • Page 101 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) three-phase current...
  • Page 102 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) three-phase reactive 01AB 400428 power demand Date of the Year: 00 to 99 Year, byte...
  • Page 103 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 01BE...
  • Page 104 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) fundamental active 01D7 400472 power of phase C 01D8 400473 Total instantaneous fundamental reactive...
  • Page 105 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) B line voltage...
  • Page 106 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Date: 1 to 31 word Date 021B 400540 Hour: 00 to 23 Hour, byte 021C...
  • Page 107 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Year: 00 to 99...
  • Page 108 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0248 400585 Maximum total active 0.000 to 99999.999 Float power 0249 400586...
  • Page 109 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Hour: 00 to 23...
  • Page 110 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0272 400627 Maximum total harmonic distortion for 0.000 to 999.999 Float 0273 400628...
  • Page 111 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) harmonic distortion for...
  • Page 112 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) harmonic distortion for Minute: 00 to 59 Minute phase C current Second: 00 to 59 word Second 029B...
  • Page 113 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) A line voltage...
  • Page 114 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) unbalance 02C7 400712 Year: 00 to 99 Year, byte 02C8 400713 Date of maximum line...
  • Page 115 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) unbalance...
  • Page 116 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 400756 voltage Date: 1 to 31 word Date 02F3 Hour: 00 to 23 (high byte) Hour, Time of maximum...
  • Page 117 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Year: 00 to 99...
  • Page 118 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0324 400805 Minimum phase A 0.000 to 99999.999 Float current 0325 400806...
  • Page 119 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) neutral line current...
  • Page 120 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Date: 1 to 31 word Date 0351 400850 Hour: 00 to 23 Hour, byte 0352...
  • Page 121 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0366...
  • Page 122 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) harmonic distortion for Month: 1 to 12 Month phase C voltage Date: 1 to 31 word Date...
  • Page 123 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) harmonic distortion for...
  • Page 124 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) voltage unbalance Year: 00 to 99 Year, Date of minimum A to byte 03A4 400933...
  • Page 125 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) unbalance...
  • Page 126 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Hour: 00 to 23 Hour, Time of minimum byte 03D0 400977 Minute...
  • Page 127 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) phase current...
  • Page 128 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) neutral current Month: 1 to 12 Month Date: 1 to 31 word Date 040F...
  • Page 129 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) phase voltage...
  • Page 130 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) current unbalance Month: 1 to 12 Month Date: 1 to 31 word Date 0433...
  • Page 131 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) apparent power...
  • Page 132 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) factor (lead) Year: 00 to 99 Year, Alarm date of byte 0456 401111...
  • Page 133 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) active power demand...
  • Page 134 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) apparent power Minute: 00 to 59 Minute demand Second: 00 to 59 word Second 0477 401144...
  • Page 135 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) over voltage...
  • Page 136 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Year: 00 to 99 Year, byte 0498 401177 Alarm date of meter Month Month: 1 to 12 reset...
  • Page 137 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Year: 00 to 99...
  • Page 138 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Setting group 10 0515 401302 Setting group 11 0516 401303 Setting group 20 051F...
  • Page 139 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 3: Average current...
  • Page 140 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 26: Phase C current 0: Disable Wh per hour by day word 056D 401390...
  • Page 141 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Time of Use #3 stop...
  • Page 142 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Time of Use #6 stop Hour: 00 to 23 (high byte) time (Applicable only byte 057F...
  • Page 143 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) DI#2 setting...
  • Page 144 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) (only applicable for #Note: Register 0x58C can DPM-C532/532M) only be written to when the operation mode is set to “Communication control”.
  • Page 145 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) IP Address...
  • Page 146 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Note: it is read-only 192) when DHCP is enabled. default gateway YYY: low byte (default: 168) (XXX.YYY.AAA.BBB)
  • Page 147 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 1: Enable...
  • Page 148 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) (XXX.YYY.AAA.BBB) IP filter#2 start BBB: low byte (default: 0) word 05BA 401467...
  • Page 149 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) the off-peak period)
  • Page 150 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) saving mode 7. Harmonics: 0x700 to 0x7FF (use only function code 0xFE to read the following parameters) The 1 harmonic for phase A voltage...
  • Page 151 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) The 21...
  • Page 152 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) The 21 harmonic for phase C current 0711 The 31 harmonic for phase C current 8.
  • Page 153 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 19: Phase B voltage...
  • Page 154 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 14. Lag PF byte 15. Lead DPF byte 16. Lag DPF byte 17.
  • Page 155 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) (high byte, type)
  • Page 156 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 0: Schedule 1: DI control (0x588 and 0x589 must be C100 Tariff mode settings set to general mode.)
  • Page 157 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 2: Exceptional days are in...
  • Page 158 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) (Setting both start time and end time to 00:00 means the time period is closed.) 0: T1 Rate type 1 for tariff...
  • Page 159 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) schedule 1...
  • Page 160 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) schedule 1 Minute: 00 to 59 (low byte) Minute (Setting both start time and end time to 00:00 means the time period is closed.)
  • Page 161 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Hour: 00 to 24 (high byte)
  • Page 162 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) schedule 2 1: T2 2: T3 3: T4 Hour: 00 to 24 (high byte) Minute: 00 to 59 (low byte) Start time 2 for tariff Hour,...
  • Page 163 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) schedule 2...
  • Page 164 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Hour: 00 to 24 (high byte) Minute: 00 to 59 (low byte) End time 6 for tariff Hour, C138...
  • Page 165 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) the time period is closed.)
  • Page 166 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) 3: T4 Hour: 00 to 24 (high byte) Minute: 00 to 59 (low byte) Start time 2 for tariff Hour, C1CD...
  • Page 167 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) end time to 00:00 means...
  • Page 168 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) (Setting both start time and end time to 00:00 means the time period is closed.) 0: T1 Rate type 6 for tariff...
  • Page 169 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) schedule 8...
  • Page 170 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) day 20 of tariff Date: 1 to 31 (low byte) Date 0: S1 1: S2...
  • Page 171 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) OFF delay time for DI2...
  • Page 172 Ch ap te r 5 Para me ters a nd Func tio ns Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Bit5: Alarm to over voltage L to N Bit6: Alarm to under voltage L to N Bit7: Alarm to over voltage unbalance...
  • Page 173 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Read Device Modbus Data (R) / Data Address Address Item Range Unit Size Type Write (Hex) (Dec) (byte) Bit7: Alarm to over current...
  • Page 174 Ch ap te r 5 Para me ters a nd Func tio ns C442 450243 Monitor State (3) Bit 0 to 15 record the status of MW (33 to 48) components (unit: bits) bits BIT: 1 indicates normal, 0 indicates abnormal C443 450244 Monitor State (4)
  • Page 175 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l C449 450250 Monitor State (10) Bit 0 to 15 record the status of MW(145 to 160) components (unit: bits) bits BIT: 1 indicates normal, 0...
  • Page 176 Ch ap te r 5 Para me ters a nd Func tio ns Modbus Communication 5.2.1 Supported Modbus Function Codes Function Modbus Name Description Code 0x03 Read Holding Registers Read the contents of read location 0x06 Preset Single Registers Preset the contents of written location 0x10 Preset Multiple Registers Preset the contents of written locations...
  • Page 177 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Write: Example: For Modbus Master, such as PLC or data collector, it uses Modbus protocol to get the value of primary-side CT setting (Register address 0x000E) on the power meter (Modbus Slave) (Slave address 0x1).
  • Page 178 Ch ap te r 5 Para me ters a nd Func tio ns The packet format for Response from Modbus Slave (power meter) is as follows: After receiving response from the power meter, Modbus Master acquires the value of currents from the primary-side current transformer (register address 0x000E), which is 1000.
  • Page 179 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l Example 1 (Individual harmonics):  If the Modbus Master (a PLC or data collector) reads recorded data from the meter with function code 0xFE in Modbus address 0x700, the Request packet format is as below (it is the same as Modbus RTU, but the Number of Points must be 1.) Master Request...
  • Page 180 Ch ap te r 5 Para me ters a nd Func tio ns Master Request 0x01 0xFE 0x08 0x00 0x00 0x01 Slave Function Start Start Number of Number of Address Code Address Address Points(Hi) Points(Lo) (Hi) (Lo) The Response packet format of the Modbus slave (Power Meter) is as below (the part before Byte Count is the same as Modbus RTU.
  • Page 181 M ul ti- fu ncti on al Powe r Me ter DPM- C53 0 Se ri es Op era tio n M anua l High byte High word Low byte … … … … … High byte Low word Low byte Selected Parameter N High byte...
  • Page 182 Chapter 6 Error Codes Table of Contents Error Codes ..................... 6-2 Alarm Types ....................6-2 Tariff Setting Errors ..................6-3 6 - 1...
  • Page 183 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l Error Codes When an error occurs during operation, the power monitor sends an error code through Modbus. The following table lists the error codes and causes.
  • Page 184 C h a p t e r 6 E r r o r C o d e s Number Alarm Type Description Lead DPF The leading power factor demand is below the setting value. Lag DPF The lagging power factor demand is below the setting value. Over Current Demand The current demand exceeds the setting value.
  • Page 185 M u l ti- func tio na l Power M e ter D PM -C53 0 Ser ies O per a ti on Ma nua l MEMO 6 - 4...
  • Page 186 Chapter 7 BACnet MS/TP (Applicable only for DPM-C530) Table of Contents BACnet Introduction ................7-2 BACnet MS/TP Support ............... 7-2 Object and Property ................7-3 AV Objects ................... 7-4 7.4.1 Commandable Analog Value Object ..........7-4 7.4.2 Read-only Analog Value Object ............7-5 BACnet MS/TP Parameter Settings ............
  • Page 187 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l BACnet Introduction BACnet is an ASHRAE, Inc.(American Society of Heating, Refrigerating and Air-Conditioning Engineer, Inc.) communication protocol for building automation and control networks.
  • Page 188 C h a p t e r 7 B A C n e t M S / T P Object and Property BACnet supports 2 object types: Device, Analog Value (AV). Please refer to the following table for the corresponding object type of each property. Object Type Property ID Property Name...
  • Page 189 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l *2.
  • Page 190 C h a p t e r 7 B A C n e t M S / T P Object No. Object Description Object Name Read/Write Range Unit 0: 3CT3PT 1: 3CT2PT 2: 3CT0PT 3: 2CT3PT AV_005_Number_of_Trans AV_005_Number_of_ AV005 R / W 4: 2CT2PT former Transformer...
  • Page 191 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l Object No.
  • Page 192 C h a p t e r 7 B A C n e t M S / T P Object No. Object Description Object Name Read/Write Range Unit 0.000 to AV 035 AV_035_Current_Neutral AV_035_Current_Neutral 99999.999 AV 036 AV_036_Unbalance_Current_A AV_036_Unbalance_Current_A 0.00 to 99.99 AV 037 AV_037_Unbalance_Current_B AV_037_Unbalance_Current_B...
  • Page 193 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l Object No.
  • Page 194 C h a p t e r 7 B A C n e t M S / T P Object No. Object Description Object Name Read/Write Range Unit AV 073 AV_073_THD_Voltage_L-L_AB AV_073_THD_Voltage_L-L_AB 0.000 to 999.999 AV 074 AV_074_THD_Voltage_L-L_BC AV_074_THD_Voltage_L-L_BC 0.000 to 999.999 AV 075 AV_075_THD_Voltage_L-L_CA AV_075_THD_Voltage_L-L_CA...
  • Page 195 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l BACnet MS/TP Parameter Settings (1) Path: Select “Menu”...
  • Page 196 C h a p t e r 7 B A C n e t M S / T P (2) Path: Select “Menu”  choose “0. Setup” and press “Enter” choose “10. BACnet” and press “Enter”  the following display is shown. Max Master: The highest MS/TP master address.
  • Page 197 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l MEMO 7 - 1 2...
  • Page 198 12 A Appendix A Accessories Table of Contents DCTMC Series ..................A-2 DCTCS Series ..................A-3 DCT1000 Series ................... A-4 DCT2000 Series ................... A-6 A - 1...
  • Page 199 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l When measured current is higher than the rated specification for the device, use of an external current transformer (CT) is necessary.
  • Page 200 Ap pen dix A Access or ies DCTCS Series External Size of Measurement Primary Secondary Wire length Model Type Dimension*1 Opening*1 Accuracy Current Current (mm) (mm) (mm) DCT-CS010-5 100 A 1000 DCT-CS020-5 200 A 1000 66.8*49.8*34.2 23.8*25.2 DCT-CS030-5 300 A 1000 DCT-CS040-5 400 A...
  • Page 201 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l DCT1000 Series Electromagnetic Compatibility: CE-marking, IEC61869-2.
  • Page 202 Ap pen dix A Access or ies Model Dimension (mm) Number External Dimension: DCT-S301C 90 x 40 x 111 DCT-S211C Size of Opening: 21 x 32 DCT-S221C DCT-S231C External Dimension: DCT-S241C 116.5 x 52 x 147 DCT-S251C Size of Opening: 50 x 80 DCT-S261C DCT-S271C External Dimension:...
  • Page 203 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l Model Dimension (mm) Number...
  • Page 204 Ap pen dix A Access or ies Model Dimension (mm) Number External Dimension: DCT-S201B 90 x 40 x 110 Size of Opening: 20 x 30 DCT-S211B DCT-S221B External Dimension: DCT-S231B 115 x 57 x 158 DCT-S241B Size of Opening: 50 x 80 DCT-S251B DCT-S261B DCT-S2C1B...
  • Page 205 M u l t i - f u n c t i o n a l P o w e r M e t e r D P M - C 5 3 0 S e r i e s O p e r a t i o n M a n u a l MEMO A - 8...
  • Page 206 Unit 2, Building A, 18-24 Ricketts Road, TEL: +39 039 8900365 Mount Waverley, Victoria 3149 Australia Mail: IA.au@deltaww.com Delta Greentech Elektronik San. Ltd. Sti. ( Turkey ) TEL: +61-1300-335-823 / +61-3-9543-3720 Şerifali Mah. Hendem Cad. Kule Sok. No:16 - A 34775 Ümraniye – İstanbul Americas Mail: Sales.IA.Turkey@deltaww.com...