3.3.2 Communication Characteristics

Communications Specifications:
Max. Communication
Distance
Max. Connection
Number
Communication
Protocols
Function Code
Use shielded twisted-pair cables for RS485 communication.
Connect the D+ communication terminal for all devices on the same twisted pair cable. Connect the D-
terminals on the other twisted pair cable. Ground the cable shield. Install a terminal resistor on the
terminal device.
Use cables with a diameter of 14–28 AWG.
3 - 6
Current
Grounding
transformer
1200 m
32
MODBUS RTU
03, 06, 10
Terminal
Voltage
block
transformer
Baud Rate
9600, 19200, 38400
Data Length
8
Parity
None, Odd, Even
Stop Bit
1