4.4. Minimum Clearance Recommended for Installation
The minimum recommended maintenance area to ensure proper airfl ow through the condenser coils and to
allow the fan to be maintained is indicated below.
B
CAIXA ELÉTRICA VOLTADA
Air circulation
Air circulation
Maintenance & Repair
Minimum
Recommended
SWITCHBOARD
PARA ESTE LADO
FACING THIS SIDE
Spacing for:
Air circulation between units:
h
d
D
CAIXA ELÉTRICA VOLTADA
SWITCHBOARD
PARA ESTE LADO
FACING THIS SIDE
Quote
Dimension (mm)
A
1000
B
600
C
500
300
D
1000
Horizontal distance to
clearance (m) - d
(in meters) - d
0,5
1
2
3
4
5
B
Minimum vertical
distance (in meters) - h
2,0
2,0
3,0
4,0
4,5
5,0
17