Carrier AQUASMART 30EX Series Installation Operation & Maintenance page 44

Air cooled scroll chiller
Table of Contents

Advertisement

5. Operation (cont.)
5. Electrical Connection:
RS485 - Closed
Protocol. It comes
from Cond. or HMI
When using an RS485 converter> 232, do not power it from the Gateway.
Reading and Writing map
Address
H0001
Type of System
H0002
Error Code
H0003
Outlet Water Temperature (INT)
H0004
Inlet Water Temperature (INT)
H0005
Outdoor Temperature
H0006
Middle Condenser Temperature
H0007
Suction Temperature
H0008
Discharge Temperature Comp.1
H0009
Discharge Temperature Comp.2
H000A
Saturated Suction Temperature
H000B
Reserve
H000C
Heatsink Temperature (Inverter only)
H000D
DIP setting
H000E
Comp Current 1 (Fixed)
H000F
Comp Current 2
H0010
Digital inputs (DI)
H0011
Digital Outputs (DO)
H0012
Comp Frequency (Inv)
H0013
Comp Current (Inv)
H0014
DC BUS Voltage (Inverter only)
H0015
Cond Motor Speed
H0016
System demand
H0017
Reserve
H0018
Mainboard Software Version
H0019
Reserve
H001A
Outlet Water Temperature (FRACTION)
44
Input Register (Function 04) - CHILLER 1
Description
GATEWAY
A1
A2
B1
B2
L N
220VAC
NOTE
See the "Type of System" table (Analyze on Hex)
Chiller <2, referring to Chiller unit. Chiller> 2, referring to the system.
See in the detailed DIP setting section
Multiply the reading by 0.25
Multiply the reading by 0.25
Bit5-0 means entries 6-1 (See Table "DI")
Bit4-0 means outputs 5-1 (See table "DO")
Multiply the reading by 0.25
RPM
%
RS485 - Modbus RTU
Protocol. Go to
Supervisory
Comment