Carrier AQUASMART 30EX Series Installation Operation & Maintenance page 62

Air cooled scroll chiller
Table of Contents

Advertisement

6. Maintenance & Repair (cont.)
ERROR
TYPE OF ERROR
CODE
Overload on
E-55
fan start
Error on Hall
E-56
Eff ect sensor
Error in the
E-57
fan board
Error in DC
E-58
bus voltage on
fan board
High temperature
E-59
on module of
fan board
E-60
Error on processor
Pressure
diff erential error
between the
inlet and outlet
E-65
water. Required
for systems with
more than 3
modules (> 45TR)
Room temperature
E-66
error <5 ° C and
crankcase resistor
Unit water low
outlet temperature
E-67
(ULWT). Freezing
protection
on cooler
62
CONSEQUENCE
of ERROR only on
Chiller 1 (Master)
Shuts off only the faulty unit, resetting
it automatically after 1 min.
Shuts off only the faulty unit, resetting
it automatically after 1 min.
It only turns off the indicated unit.
It only turns off the indicated unit,
resetting automatically after the voltage
returns to normal parameters.
Shuts off only the faulty unit, resetting
it automatically after 1 min.
It only turns off the indicated unit.
Turns off the system.
The system does not reset automatically if
the error repeats 3x in less than two hours.
Turns off the compressors.
It only turns off the inverter compressor.
The system does not reset automatically if
the error repeats 3x in less than two hours.
CONSEQUENCE
of ERROR only
on Chiller 2 to
8 (Slaves)
Check/correct:
Connection between board and
fan. Voltage on components
Replace the component(s) if required.
Check/correct:
Hall sensor hall connection
on motor board.
Replace the component(s) if required.
Check/correct:
Fan supply voltage. Connection
on the board.
Replace the component(s) if required.
Check/correct:
Board supply voltage. Connection
between board and fan.
Voltage on components -
reactor and capacitor.
Replace the component(s) if required.
Check/correct:
Board supply voltage.
Replace the component(s) if required.
De-energize the unit and re-energize it
If the problem persists, replace
the component(s).
Check/correct:
Water fl ow in the system.
If the pressure switch (DPS)
is on in the master unit.
DPS contact is opening and
closing - operational?
If the system has three units or less
and DPS is not used, make sure that
the setting is OFF in control.
The unit must not operate at temperatures
below 5 ° C. If the temperature is above
5 ° C, check the electrical connection
and physical connection of the room
Check/correct:
Outlet water temperature sensor
Water fl ow below the minimum
limit for Dirt in Y fi lter.
RECOMMENDED ACTIONS