5. Operation (cont.)
To enable or disable the differential pressure switch "DPS
Protection", follow these steps:
1.
In the "Service Access" menu use the buttons SELECIONAR
"Select" (B) to select the "DPS Protection" option.
2.
Press ALTERAR "Change" (E) up or down to select the "ON"
or "OFF", press CONFIRMAR "Enter" (D) to end.
A
AJUSTAR
CANCELAR
VERIFICAR
SELECIONAR
ALARME
DPS Protection : ON
WP : Individually
FLWD : 8°C
Mfg Setting
To set the type of pump application (WP):
1. Press SELECIONAR "Select" (B) to the "WP" option.
2. Use the buttons ALTERAR "Change" (E) up or down to
choose one of the options available, Individually (a) or
System (b):
-
Individually: 1 Pump per unit.
-
System: 1 Pump per system
A
AJUSTAR
CANCELAR
VERIFICAR
SELECIONAR
ALARME
DPS Protection : ON
WP : Individually
(a)
FLWD : 8°C
Mfg Setting
DPS Protection : ON
WP : System
(b)
FLWD : 8°C
Mfg Setting
40
B
E
D
MODO
ALTERAR
CONFIRMAR
VENTILADOR
B
E
D
MODO
ALTERAR
CONFIRMAR
VENTILADOR
To set the design's water temperature diff erence Delta
(FLWD):
1.
Press SELECIONAR "Select" (B) down to "FLWD", press
CONFIRMAR "Enter" (D).
2.
Press ALTERAR "Change" (E) up or down to choose from
3.0°C to 10°C:
A
AJUSTAR
CANCELAR
VERIFICAR
SELECIONAR
ALARME
DPS Protection : ON
WP : Individually
FLWD : 8.0°C
Mfg Setting
To Restore Factory (Default) Settings (Mfg Setting):
1.
In the "Service Access" menu use the buttons SELECIONAR
"Select" (B) to select the "System Type".
2.
Use the buttons SELECIONAR "Select" (B) again to select
the "Mfg Setting" (C) and press CONFIRMAR "Enter" (D);
A
AJUSTAR
CANCELAR
VERIFICAR
SELECIONAR
ALARME
Set Time
Time Mode: Disable
C
Timer
Mfg Setting
B
E
D
MODO
ALTERAR
CONFIRMAR
VENTILADOR
B
E
D
MODO
ALTERAR
CONFIRMAR
VENTILADOR