Type CPV...-GE-ASI-8E6A-Z M8
AS-Interface bus connection
– Voltage range (protected against incorrect
polarity)
– Residual ripple
– Max. current consumption
– all inputs 0-status
– all inputs 1-status, no current
consumption by sensors (e.g. switches)
– all inputs in 1-status, max. current
consumption by sensors
Load voltage connection
– Rated value (protected against incorrect
polarity)
– Residual ripple
– Current consumption for 8 valves
– when switched on (26.4 V)
– when switched on (20.4 V)
– after current reduction (stationary; 26.4 V)
– after current reduction (stationary; 20.4 V)
Valves (see Pneumatics manual)
Digital inputs
– Design
– Logic level
– Reference potential
– Response delay
1)
e.g. per input 30 mA, incl. 7 mA for input circuit
2
) for max. 30 ms all valve coils switched simultaneously
14
1)
2
)
2
)
Festo CPV10/14-ASI-8E6A 2018-11b English
26.5 ... 31.6 V DC
≤ 20 mVpp
CPV10-... CPV14-...
40 mA
40 mA
96 mA
96 mA
278 mA
278 mA
21.6 ... 26.4 V DC
4 Vpp
CPV10-... CPV14-...
150 mA
233 mA
120 mA
158 mA
53 mA
75 mA
68 mA
90 mA
Watchdog function
active after approx.
40 ... 100 ms (see
3.5)
8 digital inputs
based on IEC 1131-2
type 2
24 V DC, PNP,
Status display (LED)
ON: 11 ... 30 V
OFF: -30 ... 5 V
0 V
typ. 3 ms (at 24 V)