Orifice Plate Calibration Information; Flow Characteristics; Fixed Flow - Task Force Tips Master Foam Series Instructions For Installation, Operation And Maintenance

Fixed gpm self-educting foam nozzle
Hide thumbs Also See for Master Foam Series:
Table of Contents

Advertisement

5.3.3

ORIFICE PLATE CALIBRATION INFORMATION

In any eductor type system, the accuracy of proportioning depends on the viscosity of the foam concentrate. The orifice plates for the
Master Foam nozzle have been calibrated at 70 degrees F as follows:
250, 350, 500, and 750 gpm Nozzles
6.0

FLOW CHARACTERISTICS

6.1

FIXED FLOW

Pressure on this graph is the nozzle inlet pressure. Losses through piping and monitor must be taken into account to deliver the desired
pressure to the nozzle. Flow on the graph is the water flow entering the nozzle. Any foam educted adds to this flow.
500
1000
0
200
175
150
125
350 GPM
100
75
250 GPM
50
25
0
0
100
200
300
OPERATING RANGE:
150 psi (10.3 bar)MAXIMUM
50 psi (3.4 bar)MINIMUM
©Copyright Task Force Tips LLC 2015-2020
PERCENT
0.5% and 1%
3%
6%
PERCENT
1000 and 1250 gpm Nozzles
1%
3%
PERCENT
1500 and 2000 gpm Nozzles
1%
3%
1500
2000
2500
3000
500 GPM
750 GPM
400
500
600
700
800
BURST PRESSURE
1000 psi (68.9 bar)
FOAM USED FOR CALIBRATION
Class A foam of 20 centipoise viscosity
3M ATC 3 AR-AFFF product code ATC-603
3M ATC-AFFF product code FC-600F
FOAM USED FOR CALIBRATION
Williams Thunderstorm ATC AR-AFFF FC-
Williams Thunderstorm ATC AR-AFFF FC-
FOAM USED FOR CALIBRATION
National Universal Gold NFC420
National Universal Gold NFC420
Table 5.3.3
FLOW (l/min)
3500
4000
4500
5500
5000
1000 GPM
1250 GPM
900
1000
1100
1200
1300
1400
FLOW (gpm)
Figure 6.1A
11
601A
601A
6000
6500
7000
7500
1500 GPM
Table 5.3
1500
1600
1700
1800
1900
2000
LIZ-030 October 29, 2020 Rev13
8000
8500
9000
13
12
11
10
9
2000 GPM
8
7
6
5
4
3
2
1
0
2100
2200
2300

Advertisement