Advertisement

Quick Links

INSTRUCTIONS FOR INSTALLATION, OPERATION, AND MAINTENANCE
WARNING
MASTERSTREAM 1000
150 - 1000 GPM @ 100 PSI
600 - 4000 L/min @ 7 BAR (700 kPa)
MASTERSTREAM 1250
300 - 1250 GPM @ 70 - 120 PSI
1100 - 4700 L/min @ 4.8 - 8.3 BAR (480 - 830 kPa)
MASTERSTREAM 2000
300 - 2000 GPM @ 80 - 120 PSI
1100 - 7600 L/min @ 5.5 - 8.3 BAR (550 - 830 kPa)
TASK FORCE TIPS LLC
MADE IN USA · tft.com
©Copyright Task Force Tips LLC 1999-2020
Understand manual before use. Operation of this device without understanding the manual and
receiving proper training is a misuse of this equipment. Obtain safety information at tft.com/serial-
number.
This equipment is intended for use by trained and qualified emergency services personnel for
firefighting. All personnel using this equipment shall have completed a course of education
approved by the Authority Having Jurisdiction (AHJ).
This instruction manual is intended to familiarize firefighters and maintenance personnel with the
operation, servicing, and safety procedures associated with this product. This manual should be
kept available to all operating and maintenance personnel.
Masterstream
Nozzle Series
1100 - 5700 L/min @ 4.8 - 8.3 BAR (480 - 830 kPa)
2300 - 15000 L/min @ 5.5 - 8.3 BAR (550 - 830 kPa)
3701 Innovation Way, Valparaiso, IN 46383-9327 USA
1
MASTERSTREAM 1250S
150 - 1250 GPM @ 100 PSI
600 - 4500 L/min @ 7 BAR (700 kPa)
MASTERSTREAM 1500
300 - 1500 GPM @ 70 - 120 PSI
MASTERSTREAM 4000
600 - 4000 GPM @ 80 - 120 PSI
800-348-2686 · 219-462-6161 · Fax 219-464-7155
LIM-030 November 16, 2020 Rev15

Advertisement

Table of Contents
loading

Summary of Contents for Task Force Tips Masterstream Series

  • Page 1 2300 - 15000 L/min @ 5.5 - 8.3 BAR (550 - 830 kPa) TASK FORCE TIPS LLC 3701 Innovation Way, Valparaiso, IN 46383-9327 USA 800-348-2686 · 219-462-6161 · Fax 219-464-7155 MADE IN USA · tft.com ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 2 Stream reach and height at non-optimal elevations can be estimated as a factor of the performance at the optimal 30° elevation. Refer to LIM-030 and LIM-035 for effective stream trajectories of Task Force Tips Masterstream nozzles at 30° elevation. This graph cannot be used to estimate maximum reach for elevation angles below 30°.
  • Page 3: Table Of Contents

    6. Failure to follow these guidelines may result in death, burns or other severe injury. Fire and Emergency Manufacturers and Service Association FEMSA P.O. Box 147, Lynn eld, MA 01940 • www.FEMSA.org ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 4: Meaning Of Safety Signal Words

    To prevent mechanical damage, do not drop or throw equipment. NOTICE ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 5: General Information

    The Task Force Tips Masterstream Series Nozzles automatic nozzles operate by sensing the pressure at the nozzle inlet and adjusting the discharge opening to maintain a constant pressure throughout the flow range of the nozzle. While flowing, the stream pattern can be varied from wide fog to straight stream.
  • Page 6 1250, 1500, and 2000 Only) Serial Number Stream Shaper moved remotely by electricity (12-24 volts) Figure 3.1B Hydraulic Ports Serial Number Stream Shaper moved remotely by hydraulics Figure 3.1C ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 7: Specifications

    ER nozzles are equipped with manual override in case of electrical power failure. This device is not rated as ignition proof, explosion proof, or intrinsically safe. Use only in locations WARNING with adequate ventilation and no hazard of flammable vapor buildup. ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 8: Flow Characteristics

    1000 1200 1400 1600 1800 2000 Figure 4.1A MASTERSTREAM 1250s PERFORMANCE FLOW (L/MIN) 2000 4000 6000 OPERATING ENVELOPE PER NFPA 1964 1000 1200 1400 1600 FLOW (GPM) Figure 4.1B ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 9: Masterstream 1250, 1500, 2000, & 4000 (Automatic)

    7 BAR 100 PSI SETTING 6 BAR 90 PSI SETTING 80 PSI SETTING 5 BAR 70 PSI SETTING FLOW RANGE 1000 1200 1400 1600 FLOW (GPM) 1800 2000 Figure 4.2C ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 10 8 BAR 110 PSI SETTING 7 BAR 100 PSI SETTING 6 BAR 90 PSI SETTING 80 PSI SETTING FLOW RANGE FLOW (GPM) 1000 2000 3000 4000 5000 6000 Figure 4.2F ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 11: Masterstream 1000 (Selectable)

    NOZZLE FLOW (LPM) 1000 2000 3000 4000 5000 2 turns 3 turns 4 turns 5 turns 6 turns 7 turns 900 1000 1100 1200 1300 1400 NOZZLE FLOW (GPM) Figure 4.4 ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 12: Reach And Trajectory

    Figure 4.5A METERS MASTERSTREAM 1250, 70 PSI (4.8 BAR, 480 KPA) HORIZONTAL DISTANCE (FEET) CURVE FLOW REACTION CURVE FLOW REACTION 1100 1900 3000 1000 3800 1250 4700 Figure 4.5B ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 13 Figure 4.5D METERS MASTERSTREAM 1500, 70 PSI (4.8 BAR, 48 KPA) HORIZONTAL DISTANCE (FEET) CURVE FLOW REACTION CURVE FLOW REACTION 1100 2300 1000 3800 1250 4700 1500 5700 Figure 4.5E ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 14 Figure 4.5G METERS MASTERSTREAM 2000, 80 PSI (5.5 BAR, 55 KPA) HORIZONTAL DISTANCE (FEET) CURVE FLOW REACTION CURVE FLOW REACTION 1100 2300 1000 3800 1500 5700 2000 7500 Figure 4.5H ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 15 MASTERSTREAM 4000, 80 PSI (5.5 BAR, 550 KPA) HORIZONTAL DISTANCE (FEET) CURVE FLOW REACTION CURVE FLOW REACTION 2300 1000 3800 2000 7600 3000 1400 11000 4000 1900 15000 Figure 4.5K ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 16 MASTERSTREAM 4000, 120 PSI (8.3 BAR, 830 KPA) HORIZONTAL DISTANCE (FEET) FLOW REACTION FLOW REACTION CURVE CURVE 2300 1000 3800 2000 1200 7600 3000 1700 11000 4000 2300 15000 1000 Figure 4.5M ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 17: Operation

    In the event of a blockage, it may be necessary to retreat to a safe area, uncouple the nozzle and remove debris. MASTERSTREAM 1000 AND 1250S FRONT END PARTS PISTON PUSH ROD SHAFT RETURN SPRING CYLINDER Figure 5.2A ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 18 MASTERSTREAM 2000 FRONT END PARTS CONTROL POPPET SPRING SHAFT RETURN SPRING CYLINDER PISTON Figure 5.2C MASTERSTREAM 4000 FRONT END PARTS POPPET RETURN SHAFT CONTROL SPRING SPRING CYLINDER PISTON Figure 5.2D ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 19: Use With Foam

    FOAMJET LX WITH MASTERSTREAM 1000 AND 1250S NOZZLE To increase the expansion ratio, Task Force Tips “Foamjet LX” (model FJ-LX-M) may be used with the Masterstream 1000 and 1250s nozzles. This low expansion foam tube attaches and detaches quickly from the nozzle. Adjust nozzle spray pattern to give best foam quality.
  • Page 20: Warranty

    WARRANTY Task Force Tips LLC, 3701 Innovation Way, Valparaiso, Indiana 46383-9327 USA (“TFT”) warrants to the original purchaser of its products (“equipment”), and to anyone to whom it is transferred, that the equipment shall be free from defects in material and workmanship during the five (5) year period from the date of purchase.
  • Page 21: Maintenance

    FIELD LUBRICATION All Task Force Tips nozzles are factory lubricated with high quality silicone grease. This lubricant has excellent wash out resistance, providing long term performance in firefighting nozzles. If your agency has unusually hard or sandy water, the moving parts of the nozzle may be affected.
  • Page 22 MASTERSTREAM 2000 FRONT END PARTS LUBE LUBE LUBE POPPET SHAFT LUBE PISTON Figure 8.1C MASTERSTREAM 4000 FRONT END PARTS LUBE LUBE LUBE POPPET SHAFT LUBE CYLINDER PISTON Figure 8.1D ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...
  • Page 23: Service Testing

    Repair parts and service procedures are available for those wishing to perform their own repairs. Task Force Tips assumes no liability for damage to equipment or injury to personnel that is a result of user service. Contact the factory or visit the web site at tft.com for parts lists, exploded views, test procedures and troubleshooting guides.
  • Page 24: 10.0 Operation And Inspection Checklist

    Operating equipment that has failed the checklist is a misuse of this equipment. TASK FORCE TIPS LLC 3701 Innovation Way, Valparaiso, IN 46383-9327 USA 800-348-2686 · 219-462-6161 · Fax 219-464-7155 MADE IN USA · tft.com ©Copyright Task Force Tips LLC 1999-2020 LIM-030 November 16, 2020 Rev15...

Table of Contents