10K ZONE CONTROL (10K = ZoIn)
Set the 10K item to ZoIn to add indoor temperature feedback control
of multiple mixing zones. Control of mixing zones is provided by
connecting a kanmor zone control to the control. The zone control
provides its own internal mixing demand to the control. In this case,
there is no need to provide an external Mix Demand as described
earlier in Section B1. The zone control is capable of automatically
adjusting the MIX TRG temperature to improve building occupant
comfort and system performance.
10K FLOOR SENSOR (10K = Flor)
Set the 10K item to FLOR to add a floor (slab) sensor for temperature
control of a single zone mixing system. The control can use a floor
(slab) sensor to control the actual slab temperature. A floor (slab)
sensor is placed in the floor (slab) and connected to the Com and
the 10K terminals (12 and 13). Power must be applied to the Mix
Demand terminals (1 and 2) as described in Section B1. With the
floor (slab) sensor connected, the control will limit the mixing supply
temperature in order to maintain the floor (slab) sensor between the
FLOR MIN and FLOR MAX settings.
Floor Minimum (FLOR MIN)
The FLOR MIN sets the minimum allowed core temperature of the floor (slab) as long as the control is not in a WWSD.
Caution should be used when adjusting the FLOR MIN setting as this may lead to overheating of the zone during mild
conditions. If the HOL setting is selected in the Schedule menu, the control ignores the FLOR MIN setting.
Floor Maximum (FLOR MAX)
The FLOR MAX sets the maximum allowed core temperature of the slab. If the slab is to be maintained at a fixed core
temperature, set FLOR MAX and FLOR MIN items to the same setting.
ROOM TEMPERATURE UNIT (RTU) 062e, 063e
If the mixing system consists of a single zone, temperature control of
that zone can be provided by using an RTU. The RTU is connected
to the tN1/tN2 and Com terminals (11 and 12). In addition, power
must be applied to the Mix Demand terminals (1 and 2) as described
in Section B1. With the RTU connected, the control measures
the actual room temperature. With this information, the control
provides a constant water flow through the mixing system. At the
same time, indoor temperature feedback fine tunes the supply
water temperature in the mixing system to prevent over heating or
under heating. The RTU allows the user to adjust the desired room
temperature at the RTU. Remote sensor capability is also available
through an RTU as described in the RTU Data Brochure.