Monitor Menu (1 of 2)
Note: To clear the recorded information in the specific Item field, press and hold
= The Item is set to, ≠ The Item is not set to
Item Field
Access
Level
Description
The highest recorded outdoor air temperature since this item was
last cleared. This can be used to diagnose if the Outdoor Sensor
070e has been located correctly. If this reading is too high, the
070e may be located in an area that receives direct sunlight or is
influenced by an exhaust vent.
The lowest recorded outdoor air temperature since this item was
last cleared. This can be used to diagnose if the Outdoor Sensor
070e has been located correctly. If this reading is too high, the
070e may be located in an area that may not have adequate
insulation or it may be located to close to an exhaust vent.
The highest recorded temperature at the slab sensor since
this item was last cleared.
10K = FLOR
The lowest recorded temperature at the slab sensor since this
item was last cleared.
10K = FLOR
The highest recorded temperature at the mixing sensor since
this item was last cleared.
The lowest recorded temperature at the mixing sensor since
this item was last cleared.
The total number of mixing pump (Mix Pmp) running hours
since this item was last cleared.
The total number of hours the boiler has been firing since
this item was last cleared. The boiler running time may
be longer since this firing time does not include the Boil
DLY time set in the Adjust Menu. This item can be used to
determine if the boiler has been oversized or undersized
for the attached heating load. If the boiler does not run for
a high percentage of time when the outdoor temperature is
near the design temperature, the boiler has most likely been
oversized. If the boiler runs constantly but does not maintain
the building temperature at design conditions, the boiler has
been undersized.
Boil SENS = SUP
The total number of firing cycles that the boiler has had
since this item was last cleared. This item can be used in
conjunction with the Boil FIRE item to determine the average
cycle length of the boiler. The cycle length of the boiler is
related to the differential that the boiler is operating with. If
the cycle length is too short, a larger differential may allow a
longer cycle length.
Boil SENS = SUP
The highest recorded temperature at the boiler sensor since
this item was last cleared.
Boil SENS ≠ NONE
25 of 32
and .
-67 to 149°F
(-55 to 65°C)
-67 to 149°F
(-55 to 65°C)
-58 to 167°F
(-50 to 75°C)
-58 to 167°F
(-50 to 75°C)
-31 to 265°F
(-35 to 129°C)
-31 to 265°F
(-35 to 129°C)
0 to 9999 hr
0 to 9999 hr
0 to 9999
-31 to 266°F
(-35 to 130°C)
© 2003
Range
D 362e - 06/03