Advertisement

Quick Links

Mixing Control 362e
The Mixing Control 362e is a microprocessor based control designed to provide a reset mixed supply water temperature to
a heating system based on outdoor air temperature. Multiple zone temperature control can be achieved by using either a
conventional thermostat system or by using kanmor Zone Controls attached to the 362e. For single zone heating applications, a
single Room Temperature Unit (RTU) can be connected directly to the 362e for zone temperature control.
The 362e incorporates a large Liquid Crystal Display (LCD) in order to provide system status and operating information. The
same LCD is used when setting up and installing the control. Standard features include boiler return protection, intelligent boiler
operation, Warm Weather Shut Down (WWSD), and pump exercising. As well, with the addition of a new Monitor feature, it is now
possible to track pump and boiler running hours, boiler cycles and high and low sensor temperatures.
The 362e uses a floating action output signal to control the position of a mixing valve.
Mixing Control 362e
Floating Action
Input
Mix
Demand
signal
Input
230 V (ac)
Power
Supply
Output
Mixing
System
Pump
Output
Boiler
- Data Brochure
Item
Menu
1 2
3
4 5
Mix
Power
Mix
Demand
N
L
Pmp
M
Input
Output
Room
Mixing Valve &
Temperature
Actuating Motor
Unit (RTU)
Mix Demand
WWSD
Minimum
Maximum
INSTALLATION CATEGORY II
Made in Canada
Power:
Relays:
Demand:
Signal wiring must be rated at least 300 V.
6 7 8 9
10
11 12 13 14
Boiler
Pwr Opn Cls
tN1/ Com 10K UnO Com Mix Boil Out
Mix
tN2
OR
OR
Input
Remote
Display
Module (RDM)
Indoor Sensor or Zone Control
1 of 32
Setback
None
Test
230 V ±10% 50/60 Hz 2300 VA
230 V (ac) 10 A 1/3 hp, pilot duty 240 VA
20 to 260 V (ac) 2 VA
Do not apply power
15
16
17 18
Sw
OR
Input
kanmor Slab Sensor, or
© 2003
D 362e
06/03
Input
Outdoor
Sensor
Included
Input
Universal Sensor
Included
Input
Universal Sensor
Included
Input
kanmor
timer
D 362e - 06/03

Advertisement

Table of Contents
loading

Summary of Contents for Kanmor Mixing Control 362e

  • Page 1 Mixing Control 362e 06/03 The Mixing Control 362e is a microprocessor based control designed to provide a reset mixed supply water temperature to a heating system based on outdoor air temperature. Multiple zone temperature control can be achieved by using either a conventional thermostat system or by using kanmor Zone Controls attached to the 362e.
  • Page 2: Table Of Contents

    How To Use The Data Brochure This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and 4) Troubleshooting. The Sequence of Operation section has three sub sections. We recommend reading Section A: General Operation, as this contains important information on the overall operation of the control.
  • Page 3: Description Of Display Elements

    Display Item Field Number Field Displays an abbreviated Displays the current value name of the selected item of the selected item Menu Field Displays the current menu Status Field Displays the current status of the control Buttons inputs, outputs and Selects Menus, operation Items and...
  • Page 4: Sequence Of Operation

    POWERING UP THE CONTROL When the Mixing Control 362e is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the current outdoor air temperature.
  • Page 5: Section B: Mixing Reset

    Section B: Mixing Reset Section B1 Section B2 General Alternate Mixing Mixing Operation Demand Section B1: General Mixing Operation MIXING DEMAND A mixing demand is generated by applying a voltage between 24 and 230 V (ac) across the Mix Demand terminals (1 and 2). Once voltage is applied, the Mix Demand pointer is displayed in the LCD.
  • Page 6 MIXING TARGET TEMPERATURE (MIX TRG) The MIX TRG temperature is determined from the Characterized Heating Curve settings and the outdoor air temperature. The control displays the temperature that it is currently trying to maintain as the mixing supply temperature. If the control does not presently have a requirement for heat, it displays “–...
  • Page 7 10K INDOOR SENSOR (10K = INDR) Set the 10K item to INDR to add an indoor sensor for temperature Indoor kanmor control of a single zone mixing system. The indoor sensor is Sensor 362e Control connected to the Com and 10K terminals (12 and 13).
  • Page 8 Set the 10K item to ZoIn to add indoor temperature feedback control of multiple mixing zones. Control of mixing zones is provided by connecting a kanmor zone control to the control. The zone control provides its own internal mixing demand to the control. In this case, there is no need to provide an external Mix Demand as described earlier in Section B1.
  • Page 9: Section C: Boiler Operation

    Section C: Boiler Operation Section C1 Section C2 Section C3 Boiler Supply Boiler Return No Boiler Sensor Sensor Sensor Section C1: Boiler Supply Sensor BOILER SENSOR ON THE SUPPLY (Boil SENS = SUP) The boiler sensor can be located on the boiler supply if the 362e is the only control that is operating the boiler.
  • Page 10 BOILER FIRE DELAY (Boil DLY) The Boil DLY is the delay time that may happen between the time that the control closes the boiler contact and the burner fires. This delay is usually the result of a burner pre-purge or other forms of time delay built into the burner’s safety circuits. BOILER MASS (Boil MASS) The Boil MASS setting allows the control to adjust to different types of heat sources depending on their thermal mass.
  • Page 11: Installation

    Type 362e includes: One Mixing Control 362e, One Outdoor Sensor 070e, Two Universal Sensors 071e Data Brochures D 362e, D 070e, User Brochure U 362e, Essay E 007e. Note: Carefully read the details of the Sequence of Operation to ensure that you have chosen the proper control for your application.
  • Page 12: Electrical Connections

    If a Remote Display Module (RDM) 040e is used, install the RDM according to the installation instructions in Data Brochure D 040e and run the wiring back to the control. • If a kanmor Zone Control is used, run the wires from the Zone Control to the 362e. Refer to the instructions supplied with the Zone Control. •...
  • Page 13 Zone Control Zone Control Input If an external kanmor Zone Control is used, connect the wire from the Com Sen terminal on the Zone Control to the Com terminal (12) on the 362e. Connect the Zo Out terminal on the Zone Control to the 10K terminal (13) on the 362e.
  • Page 14: Testing The Wiring

    UnOccupied Switch If an external timer or switch is used, connect the two wires from the external switch to the Com and UnO Sw terminals (12 and 14). When these two terminals are shorted together, the control registers an UnOccupied signal. Note: The setback override in the schedule menu of the control overrides any external signal that is present on the UnOccupied Switch terminals.
  • Page 15 Boiler If the boiler is connected to the Boiler terminals (6 and 7), make sure power to the boiler circuit is off and install a jumper between the terminals. When the boiler circuit is powered up, the boiler should fire. If the boiler does not turn on, refer to any installation or troubleshooting information supplied with the boiler.
  • Page 16: Dip Switch Settings

    UnO Sw terminal. Access Levels The kanmor Mixing Control 362e comes with four Access Level set- tings. These Access Levels restrict the number of Menus, Items, and Adjustments that can be accessed by the user. The four ac- cess levels are Limited (LTD), User (USER), Installer (INST) and Advanced (ADV).
  • Page 17: Control Settings

    -58 to 167°F Measured room air temperature at the indoor sensor. (-50 to 75°C) 10K = INDR This is the signal that is being received from a kanmor – – –, 35 to 110°F Zone Control. (– – –, 2 to 43°C) 10K = ZoIn Current floor (slab) sensor temperature.
  • Page 18: Adjust Menu

    Adjust Menu (1 of 2) Note: = The Item is set to, ≠ The Item is not set to Access Actual Level Item Field Description Range Setting The desired room air temperature during an 35 to 100°F Occupied period. (2 to 38°C) Note: There is only a ±3°F (±1°C) adjustment in Default = 70°F the LTD access level.
  • Page 19 Adjust Menu (2 of 2) Note: = The Item is set to, ≠ The Item is not set to Access Level Actual Item Field Description Range Setting The time that the actuating motor requires to 30 to 230 sec operate from fully closed to fully open. Default = 150 sec SUP (Supply) RET (Return)
  • Page 20: Schedule Menu

    Room Temperature Units (RTUs) 062e and 063e A single RTU may be connected to the Mixing Control 362e in order to provide the control with indoor temperature feedback for the mixing side of the heating system. When using an RTU, several items related to the mixing side of the heating system are no longer available in the control’s User...
  • Page 21 RTU View Menu (2 of 2) Note: = The Item is set to, ≠ The Item is not set to Access Level Item Field Description Range -67 to 149°F Current outdoor air temperature. (-55 to 65°C) Current floor (slab) sensor temperature. -58 to 167°F REMOTE 3 = FLOR (-50 to 75°C)
  • Page 22 RTU Monitor Menu (1 of 1) Access Actual Level Item Field Description Range Setting The highest outdoor air temperature recorded -67 to 149°F since this item was last cleared. (-55 to 65°C) To clear, press & hold the & buttons The lowest outdoor air temperature recorded -67 to 149°F since this item was last cleared.
  • Page 23: Testing And Troubleshooting

    MAX HEAT (MAX HEAT) The Mixing Control 362e has a function called MAX Heat. In this mode, the control turns on and operates the system up to the maximum set temperatures, and the mixing device at the set percentage, as long as there is a demand for heat. The control continues to operate in this mode for up to 24 hours or until either the Item, Menu or Test button is pressed.
  • Page 24 Troubleshooting When troubleshooting any heating system, it is always a good idea to establish a set routine to follow. By following a consistent routine, many hours of potential headaches can be avoided. Below is an example of a sequence that can be used when diagnosing or troubleshooting problems in a hydronic heating system.
  • Page 25: Monitor Menu

    Monitor Menu (1 of 2) Note: To clear the recorded information in the specific Item field, press and hold and . = The Item is set to, ≠ The Item is not set to Access Level Item Field Description Range The highest recorded outdoor air temperature since this item was last cleared.
  • Page 26: Error Messages

    Monitor Menu (2 of 2) Note: To clear the recorded information in the specific Item field, press and hold and . Access Level Item Field Description Range The lowest temperature recorded at the boiler sensor since this -31 to 266°F item was last cleared.
  • Page 27 Error Messages (2 of 4) Error Displayed Description of Error The control was unable to read a piece of information stored in the Schedule menu. Because of this, the control was required to load the factory settings into all of the items in the Schedule menu. The control will continue to display the error message until all of the items available in the Schedule menu of the control have been checked by the user or installer.
  • Page 28 Error Messages (3 of 4) Error Displayed Description of Error The control is no longer able to read the Outdoor sensor due to an open circuit. In this case the control assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the problem.
  • Page 29 Error Messages (4 of 4) Error Displayed Description of Error The Remote Sensor 2 attached to the RTU is being read as a short circuit. The RTU will continue operation using all remaining sensors. If all of the sensors are unavailable, the control will continue to operate as if the RTU was not connected to the control.
  • Page 30 Notes © 2003 D 362e - 06/03 30 of 32...
  • Page 31 Notes 31 of 32 © 2003 D 362e - 06/03...
  • Page 32: Technical Data

    Limited Warranty and Product Return Procedure Limited Warranty The liability of kanmor Control Systems Ltd. to its customers which are different from or in excess of the kanmor Limited (“kanmor”) under this warranty is limited. The Purchaser, by taking Warranty are the Purchaser’s sole responsibility and obligation. Purchaser receipt of any kanmor product (“Product”), acknowledges the terms...

Table of Contents