Kanmor Mixing Control 362e Data Brochure page 27

Table of Contents

Advertisement

Error Messages (2 of 4)
Error Displayed
The control was unable to read a piece of information stored in the Schedule menu. Because of this,
the control was required to load the factory settings into all of the items in the Schedule menu. The
control will continue to display the error message until all of the items available in the Schedule menu
of the control have been checked by the user or installer.
Note: Access level must be ADV in order to clear the error.
The control was unable to read a piece of information stored in the Miscellaneous menu. Because
of this, the control was required to load the factory settings into all of the items in the Miscellaneous
menu. The control will continue to display the error message until all of the items available in the
Miscellaneous menu of the control have been checked by the user or installer.
Note: Access level must be ADV in order to clear the error.
The RTU was unable to store a piece of information to the EEPROM. This error can be caused by
a noisy power source to the control. The control will display the error message and will continue to
operate as normal. To clear this error, press either the Menu or Item buttons.
The RTU was unable to read a piece of information stored in the Adjust Menu. Because of this, the
control was required to load the factory settings into all of the items in the Adjust Menu. The control
will operate based on only the Characterized Heating Curve settings until all of the items available in
the Adjust Menu of the RTU have been checked by the user or installer.
Note: Access level must be ADV in order to clear the error.
The RTU was unable to read a piece of information stored in the Monitor Menu. Because of this, the
control was required to load the factory settings into all of the items in the Monitor Menu. The control
will continue to display the error message until all of the items available in the Monitor Menu of the
RTU have been checked by the user or installer.
Note: Access level must be ADV in order to clear the error.
The RTU was unable to read a piece of information stored in the Schedule menu. Because of this,
the control was required to load the factory settings into all of the items in the Schedule menu. The
control will continue to display the error message until all of the items available in the Schedule menu
of the RTU have been checked by the user or installer.
Note: Access level must be ADV in order to clear the error.
The RTU was unable to read a piece of information stored in the Miscellaneous menu. Because of
this, the control was required to load the factory settings into all of the items in the Miscellaneous
menu. The control will continue to display the error message until all of the items available in the
Miscellaneous menu of the RTU have been checked by the user or installer.
Note: Access level must be ADV in order to clear the error.
An incorrect device has been connected to the tN1/tN2 input terminal. Once the problem has been
corrected, press either the Menu or Item button to clear the error message from the control.
A short circuit has been read between the tN1/tN2 terminal and a Com terminal on the control. Either
the wires leading to the tN1/tN2 device are shorted or the polarity of the wires is reversed. Determine
the cause and remove the short. To clear this error, press either the Menu or Item buttons.
The control is no longer able to read the information that is coming from the RTU. Reconnect the
RTU and press either the Menu or Item button to clear the error. If the RTU has been deliberately
disconnected from the control, remove power from the control for 10 seconds and then re-power the
control in order to clear the error message.
The control is no longer able to read the Outdoor sensor due to a short circuit. In this case the control
assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the
problem. To clear the error message from the control after the sensor has been repaired, press either
the Menu or Item button.
Description of Error
27 of 32
© 2003
D 362e - 06/03

Advertisement

Table of Contents
loading

Related Products for Kanmor Mixing Control 362e

Table of Contents