RTU View Menu (2 of 2)
Note: = The Item is set to, ≠ The Item is not set to
Item Field
RTU Adjust Menu (1 of 1)
Note: = The Item is set to, ≠ The Item is not set to
Item Field
Occ
UnOcc
Access
Level
Current outdoor air temperature.
Current floor (slab) sensor temperature.
B2
REMOTE 3 = FLOR
Access
Level
The desired room air temperature during
an Occupied period for the heating zone.
B1
Note: There is only a ±3°F (±1°C)
adjustment in the LTD access level
The desired room air temperature during an
UnOccupied period for the heating zone.
B1
Note: There is only a ±3°F (±1°C)
adjustment in the LTD access level
DIP switch = Setback
The amount of morning boost.
B1
DIP switch = Setback
Selects whether the RTU is to use its
internal air sensor.
This item allows for remotely adding a 10K
sensor to the RTU. Applications are for
temperature averaging.
This item allows for remotely adding
a second 10K sensor to the RTU.
Applications
averaging.
This item allows for remotely adding a
third 10K air sensor to the RTU, or a 10K
slab sensor to measure slab temperature.
MIX MIN = OFF (for Slab Sensor only)
The minimum target temperature at the
floor (slab) sensor when not in WWSD.
REMOTE 3 = FLOR
The maximum target temperature at the
flor (slab) sensor.
REMOTE 3 = FLOR
Description
Description
are
for
temperature
21 of 32
Range
-67 to 149°F
(-55 to 65°C)
-58 to 167°F
(-50 to 75°C)
Actual
Range
Setting
35 to 100°F
(2 to 38°C)
Default = 70°F
(21°C)
35 to 100°F
(2 to 38°C)
Default = 65°F
(18°C)
OFF, 0:20 to 8:00 hr
Default = OFF
OFF, AIR
Default = AIR
NONE, AIR
Default = NONE
NONE, AIR
Default = NONE
NONE, AIR,
FLOR
Default = NONE
OFF, 35 to 120°F
(OFF, 2 to 49°C)
Default = 70°F
(21°C)
40 to 150°F
(4 to 66°C)
Default = 90°F
(32°C)