Adjust Menu - Kanmor Mixing Control 362e Data Brochure

Table of Contents

Advertisement

Adjust Menu (1 of 2)
Note: = The Item is set to, ≠ The Item is not set to
Item Field
Occ
UnOcc
© 2003
D 362e - 06/03
Access
Level
The desired room air temperature during an
Occupied period.
B1
Note: There is only a ±3°F (±1°C) adjustment in
the LTD access level.
No RTU connected
The desired room air temperature during an
UnOccupied period.
B1
Dip switch = Setback
No RTU connected
The device that is to be connected to the 10K
B2
input terminal.
No RTU connected
The minimum temperature at the floor (slab)
sensor as long as the control is not in WWSD.
B2
10K = FLOR
MIX MIN = OFF
No RTU connected
The maximum temperature at the floor (slab)
sensor.
B2
10K = FLOR
MIX MIN = OFF
No RTU connected
The amount of morning boost.
Dip switch = Setback
B1
No RTU connected
10K ≠ ZoIn
The type of terminal units that are being used in
B1
the heating system.
The minimum supply water temperature for the
B1
mixing system.
The design indoor air temperature used in the
B1
heat loss calculations for the heating system.
The design supply water temperature used in the
B1
heat loss calculations for the heating system.
The design outdoor air temperature used in the
B1
heat loss calculations for the heating system.
The maximum supply water temperature for the
B1
mixing system.
Description
18 of 32
Actual
Range
Setting
35 to 100°F
(2 to 38°C)
Default = 70°F
(21°C)
35 to 100°F
(2 to 38°C)
Default = 65°F
(18°C)
NONE, INDR,
ZoIn, FLOR, (only)
if MIX MIN = OFF
Default = NONE
OFF, 35 to 120°F
(OFF, 2 to 49°C)
Default = 70°F
(21°C)
40 to 150°F
(4 to 66°C)
Default = 90°F
(32°C)
OFF, 0:20 to 8:00 Hr
Default = OFF
U/F1 (Screeded),
U/F2 (Plated), UNIT,
FIN, RAD(iator),
BASE(board)
Default = U/F1
OFF, 35 to 150°F
(OFF, 2 to 66°C)
Default = OFF)
35 to 100°F
(2 to 38°C)
Default = 70°F
(21°C)
70 to 220°F
(21 to 104°C)
Default = 120°F
(49°C)
-60 to 32°F
(-51 to 0°C)
Default = 10°F
(-12°C)
80 to 212°F
(27 to 99°C)
Default = 140°F
(60°C)