Adjust Menu (2 of 2)
Note: = The Item is set to, ≠ The Item is not set to
Item Field
Occ
UnOcc
Access
Level
The time that the actuating motor requires to
operate from fully closed to fully open.
C1
The location of the boiler sensor. This affects
C2
operation of the boiler contact.
C3
The maximum temperature allowed for the boiler
C1
target temperature.
Boil SENS = SUP
The minimum temperature allowed for the boiler
C1
target temperature.
Boil SENS ≠ NONE
The time delay the control can expect between the
C1
time the boiler contact closes and the burner fires.
Boil SENS = SUP
The thermal mass characteristics of the boiler
C1
that is being used.
Boil SENS = SUP
The differential that the control is to use when it is
C1
operating the boiler.
Boil SENS = SUP
The system's warm weather shut down during the
B1
Occupied period.
The system's warm weather shut down during the
B1
UnOccupied period.
Dip switch = Setback
The maximum length of time that the boiler pump
B1
will continue to operate after the mixing demand
has been removed.
Enables or disables the Soft Start feature in the
B1
control.
The frequency with which the control will
A
exercise the pumps and valves that are
operated by the control.
Description
19 of 32
Actual
Range
Setting
30 to 230 sec
Default = 150 sec
SUP (Supply)
RET (Return)
NONE
Default = SUP
120 to 225°F, OFF
(49 to 107°C, OFF)
Default = 210°F
(99°C)
OFF, 80 to 180°F
(OFF, 27 to 82°C)
Default = 140°F
(60°C)
0:00 to 3:00 min
(1 sec. increments)
Default = 0:10 min
LITE, MED,
HEVY
Default = MED
AUTO, 2 to 42°F
(AUTO, 1 to 23°C)
Default = AUTO
35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 70°F
(21°C)
35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 60°F
(16°C)
OFF,
0:10 to 40:00 min
Default = 0:20
min
NONE, MIX
Default = NONE
30 to 240 hr,
OFF
Default = 70 hr